80459-641-01E
Model 6 Motor Control Centers
10/2012
Section 11—Troubleshooting
© 1999–2012 Schneider Electric All Rights Reserved
101
ENGLISH
Table 17:
Motor Control Center Troubleshooting Chart
Part
Problem
Cause
Remedy
Contacts
Contact Chatter (also
see Noisy Magnet)
1. Poor contact in the control circuit.
1. Replace the contact device or use a holding circuit interlock
(3-wire control).
2. Low voltage.
2. Check the coil terminal voltage and voltage dips during starting.
Welding or Freezing
1. Abnormal inrush of current.
1. Check for grounds, shorts, or excessive motor load current, or
use larger contactor.
2. Rapid jogging.
2. Install a larger device rated for jogging service.
3. Insufficient tip pressure.
3. Replace contacts and springs. Check contact carrier for
deformation or damage.
4. Low voltage which prevents the magnet
from sealing.
4. Check the coil terminal voltage and voltage dips during starting.
5. Foreign matter prevents the contacts
from closing.
5. Clean the contacts with an environmentally safe (CFC-free)
contact cleaner.
6. Short circuit or ground fault.
6. Remove the fault. Ensure that the fuse and circuit breaker sizes
are correct.
Short Trip Life or
Overheating or Trips
1. Filing or dressing.
1. Do not file the silver tips; rough spots or discoloration do not
harm tips or impair their efficiency.
2. Interrupting excessively high currents.
2. Install a larger device or check for grounds, shorts, or excessive
motor currents.
3. Excessive jogging.
3. Install a larger device rated for jogging service.
4. Weak tip pressure.
4. Replace contacts and springs; check the contact carrier for
deformation or damage.
5. Dirt or foreign matter on the contact
surface.
5. Clean contacts with an environmentally safe (CFC-free) contact
cleaner. Reduce the entry of foreign matter into the enclosure.
6. Short circuit or ground fault.
6. Remove the fault; ensure that the fuse and circuit breaker sizes
are correct.
7. Loose connection in the power circuit.
7. Clear and tighten the connection.
8. Sustained overload.
8. Check for excessive motor load current or install a larger
device.
Coils
Open Circuit
Mechanical damage.
Replace the coil; handle and store replacement coils carefully.
Overheated Coil
1. Overvoltage or high ambient
temperature.
1. Check the coil terminal voltage. It should not exceed 110% of
the coil rating.
2. Incorrect coil.
2. Install the correct coil.
3. Shorted turns caused by mechanical
damage or corrosion.
3. Replace the coil.
4. Undervoltage; failure of the magnet to
seal in.
4. Check the coil terminal voltage. It should be at least 85% of the
coil rating.
5. Dirt or rust on the pole faces.
5. Clean the pole faces.
6. Mechanical obstruction.
6. With power
off
, check for free movement of the contact and
armature assembly.
Thermal Overload
Relays
Tripping
1. Sustained overload.
1. Check for excessive motor currents or current unbalance;
correct cause.
2. Loose or corroded connection in the
power circuit.
2. Clean and tighten the connection.
3. Incorrect thermal units.
3. Replace the thermal units with the correct size for the
application.
4. Excessive coil voltage.
4. Voltage should not exceed 110% of the coil rating.
Failure To Trip
1. Incorrect thermal units.
1. Check the thermal unit selection table. Install the proper thermal
units.
2. Mechanical binding, dirt, corrosion, etc.
2. Replace the relay and thermal units.
3. Relay previously damaged by a short
circuit.
3. Replace the relay and thermal units.
4. Relay contact welded or not in series with
the contactor coil.
4. Check circuit for a fault and correct the condition. Replace the
contact or the entire relay as necessary.
Summary of Contents for sc200
Page 5: ...DOC023 53 80040 sc200 Controller 01 2014 Edition 7 User Manual ...
Page 6: ......
Page 10: ...Table of Contents 4 ...
Page 20: ...14 nglisK ...
Page 23: ... nglisK 17 ...
Page 53: ......
Page 56: ...Visit us at www hach com ...
Page 74: ...20 Installation ...
Page 90: ...Visit us at www hach com Maintenance ...
Page 96: ...Visit us at www hach com ...
Page 100: ...Visit us at www hach com ...
Page 106: ...Visit us at www hach com ...
Page 108: ...Visit us at www hach com ...
Page 110: ...Visit us at www hach com ...
Page 115: ......
Page 148: ...Figure 4 5 Transistor Outputs 4 8 ...
Page 176: ...Figure 8 1 Dimensions 8 2 ...
Page 195: ......
Page 256: ......
Page 257: ......
Page 258: ......
Page 259: ......
Page 265: ...Figure 1 1 Typical ModBUS Network Topography 1 3 ...
Page 267: ...Figure 1 2 Typical Communications Wiring Scheme 1 5 ...
Page 268: ...Figure 1 3 Signal Boost Sensor Diagram 1 6 ...
Page 270: ...Figure 2 1 Typical Communication Cable Wiring for Signal Boost Option 2 2 ...
Page 271: ...Figure 2 2 Sensor Display Screens 2 3 ...
Page 290: ......
Page 292: ......
Page 348: ...PAGE 54 APPENDIX D MOUNTING 15 APPENDIX D MOUNTING Figure 9 Mounting Detail ...
Page 351: ......
Page 352: ...Powerware Series Eaton 9130 UPS 700 3000 VA User s Guide ...
Page 472: ... 0 5 3 5 6 A B 3 4 ñ 4 9 0 ñ ñ ñ 2 ñ 5 7 8 1 5 CB N4 C N4 9 2 2 6 9 E 3 7 2 5 0 0 2 3 2 ...
Page 473: ... 0 5 3 5 6 A B 3 4 ñ 4 9 0 ñ ñ ñ 2 ñ 5 5 3 0 44 7 3 7 4 2 K 3 50 0 ...
Page 476: ......
Page 477: ......
Page 479: ......
Page 555: ......
Page 556: ......
Page 557: ......
Page 558: ......
Page 559: ......
Page 560: ......
Page 561: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 562: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 563: ...UNIT HEATERS FOR STEAM OR HOT WATER Rosemex Products HEATING 01 2003 ...
Page 571: ......
Page 579: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 584: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 Ƭ ...
Page 594: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ȋ Ȍ ...
Page 624: ......
Page 625: ......
Page 626: ......
Page 627: ......
Page 628: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 636: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 637: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......
Page 644: ......
Page 645: ......
Page 646: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ǡ ǡ ...
Page 650: ... 2014 Pentair Equipment Protection PH 763 422 2211 hoffmanonline com 87563688 4 M5 9 1 2 3 4 ...
Page 651: ... 2014 Pentair Equipment Protection PH 763 422 2211 hoffmanonline com 87563688 5 ...
Page 653: ... 2014 Pentair Equipment Protection PH 763 422 2211 hoffmanonline com 87563688 7 3 3 7 7 3 3 ...
Page 654: ... 2014 Pentair Equipment Protection PH 763 422 2211 hoffmanonline com 87563688 8 1 2 4X 8X 1X ...
Page 672: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 805: ...Notes ENGLISH ...
Page 806: ...Notes ENGLISH ...
Page 807: ...Notes ENGLISH ...
Page 809: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 810: ......
Page 811: ......
Page 812: ......
Page 861: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 862: ......
Page 863: ......
Page 864: ......
Page 865: ......
Page 866: ......
Page 867: ......
Page 868: ......
Page 869: ......
Page 870: ......
Page 871: ......
Page 872: ......
Page 873: ......
Page 874: ......
Page 875: ......