![Hach sc200 User Manual Download Page 581](http://html.mh-extra.com/html/hach/sc200/sc200_user-manual_576786581.webp)
5) Damper and actuator must be kept clean, dry and protected from dirt, dust and other foreign materials prior to and after installation.
Common examples of such foreign materials include sawdust, mortar dust, drywall dust, fireproofing materials, plaster and paint
overspray.
6) Damper should be sufficiently covered as to prevent overspray if wall texturing or spray painting will be performed within 10 feet
(3m) of the damper. Excessive dirt or foreign material deposits on damper can cause excessive leakage and/or torque requirements to
exceed damper/actuator design.
7) Suitable access to dampers and actuators must be provided for damper inspection, maintenance and servicing. Where it is not
possible to achieve sufficient size access, it will be necessary to install a removable section of duct.
Electrical Guidelines:
All electrical and or pneumatic connections to damper actuators should be made in accordance with applicable codes,
ordinances and regulations.
SAFETY DANGER!
Electrical input may be needed for this equipment. This
work should be performed by a qualified electrician.
SAFETY CAUTION!
Verify power requirements before wiring actuator.
Alumavent is not responsible for any damage to, or
failure of the unit caused by incorrect field wiring.
Electrical and/or pneumatic connections to damper actuators
should be made in accordance with wiring and piping
diagrams developed in compliance with applicable codes,
ordinances and regulations.
Installation Instructions:
IMPORTANT: Failure to follow instructions will void all warranties.
1. INSTALLING MULTIPLE SECTION DAMPERS:
A damper assembly is not restricted to a maximum number of sections, but must not exceed the maximum section sizes shown below.
These dampers are intended to be self supporting only in their largest single section size. Multiple section damper assemblies may
require bracing to support the weight of the assembly and to hold against system pressure. Alumavent recommends appropriate
bracing to support the damper horizontally. Support ductwork in area of damper to prevent sagging due to damper weight.
Cycle the dampers by hand before installation to ensure freedom of movement.
Fasten damper sections together with #10 x ¾
”
(19mm) sheet metal screws, ¼ in.
(6mm) diameter nuts and bolts, tack or spot welds.
Attachments should be spaced a maximum of 6
” (152mm)
on centers and a
maximum of 3
”
(76mm) from corners. Attachments must be made on both front
face and back face (air entering and air exiting sides) of damper sections.
2. If more than three sections wide, unit ships as multiple section assemblies for assembly in the field. Assemblies are to be joined
together where the jackshaft extends past the frame 4 inches (102mm).
3. Duct opening or opening square should measure
¼”
(6mm) larger than damper dimension and should be straight
and level.
4. If no holes are present in frame, drill appropriate size holes as necessary , depending on fastener type, on 6
”
(152mm) centers
and fasten frames together.
5. Use shims between damper frame and duct opening or opening space to prevent distortion of frame by fasteners
holding it in place. Brace at every horizontal mullion and vertically brace at every 8 feet of damper width for
strength. Dampers subjected to high velocities (2000 fpm [10.2 m/s]) may require more bracing. Note: Alumavent dampers
are specifically designed and engineered for structural integrity based on model and conditions. Attachment, framing,
mating flanges, and anchoring of damper assemblies into openings, ductwork, or walls is the responsibility of the installer. Design
calculations for these retaining and supporting members should be determined by field engineers for that particular installation.
6. If damper actuator is to be mounted out of the air stream, the extension pin should extend approximately 4 inches (102mm)
beyond the frame. On jack shafted units, the jackshaft should extend through the jackshaft bearing assembly and approximately
6 inches (152mm) beyond the frame.
Page 2 of 4
Damper
Model
Series
Max. Single
Section Size
Max. Size for
Multi-Section
Dampers
3100 & 3900
48
”w
x
60”h
(1219 x 1524)
Unlimited
4000 & 4100
48
”w
x 72
”h
(1219 x 1829)
Unlimited
Summary of Contents for sc200
Page 5: ...DOC023 53 80040 sc200 Controller 01 2014 Edition 7 User Manual ...
Page 6: ......
Page 10: ...Table of Contents 4 ...
Page 20: ...14 nglisK ...
Page 23: ... nglisK 17 ...
Page 53: ......
Page 56: ...Visit us at www hach com ...
Page 74: ...20 Installation ...
Page 90: ...Visit us at www hach com Maintenance ...
Page 96: ...Visit us at www hach com ...
Page 100: ...Visit us at www hach com ...
Page 106: ...Visit us at www hach com ...
Page 108: ...Visit us at www hach com ...
Page 110: ...Visit us at www hach com ...
Page 115: ......
Page 148: ...Figure 4 5 Transistor Outputs 4 8 ...
Page 176: ...Figure 8 1 Dimensions 8 2 ...
Page 195: ......
Page 256: ......
Page 257: ......
Page 258: ......
Page 259: ......
Page 265: ...Figure 1 1 Typical ModBUS Network Topography 1 3 ...
Page 267: ...Figure 1 2 Typical Communications Wiring Scheme 1 5 ...
Page 268: ...Figure 1 3 Signal Boost Sensor Diagram 1 6 ...
Page 270: ...Figure 2 1 Typical Communication Cable Wiring for Signal Boost Option 2 2 ...
Page 271: ...Figure 2 2 Sensor Display Screens 2 3 ...
Page 290: ......
Page 292: ......
Page 348: ...PAGE 54 APPENDIX D MOUNTING 15 APPENDIX D MOUNTING Figure 9 Mounting Detail ...
Page 351: ......
Page 352: ...Powerware Series Eaton 9130 UPS 700 3000 VA User s Guide ...
Page 472: ... 0 5 3 5 6 A B 3 4 ñ 4 9 0 ñ ñ ñ 2 ñ 5 7 8 1 5 CB N4 C N4 9 2 2 6 9 E 3 7 2 5 0 0 2 3 2 ...
Page 473: ... 0 5 3 5 6 A B 3 4 ñ 4 9 0 ñ ñ ñ 2 ñ 5 5 3 0 44 7 3 7 4 2 K 3 50 0 ...
Page 476: ......
Page 477: ......
Page 479: ......
Page 555: ......
Page 556: ......
Page 557: ......
Page 558: ......
Page 559: ......
Page 560: ......
Page 561: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 562: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 563: ...UNIT HEATERS FOR STEAM OR HOT WATER Rosemex Products HEATING 01 2003 ...
Page 571: ......
Page 579: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 584: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 Ƭ ...
Page 594: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ȋ Ȍ ...
Page 624: ......
Page 625: ......
Page 626: ......
Page 627: ......
Page 628: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 636: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 637: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 638: ......
Page 639: ......
Page 640: ......
Page 641: ......
Page 642: ......
Page 643: ......
Page 644: ......
Page 645: ......
Page 646: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ǡ ǡ ...
Page 650: ... 2014 Pentair Equipment Protection PH 763 422 2211 hoffmanonline com 87563688 4 M5 9 1 2 3 4 ...
Page 651: ... 2014 Pentair Equipment Protection PH 763 422 2211 hoffmanonline com 87563688 5 ...
Page 653: ... 2014 Pentair Equipment Protection PH 763 422 2211 hoffmanonline com 87563688 7 3 3 7 7 3 3 ...
Page 654: ... 2014 Pentair Equipment Protection PH 763 422 2211 hoffmanonline com 87563688 8 1 2 4X 8X 1X ...
Page 672: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 805: ...Notes ENGLISH ...
Page 806: ...Notes ENGLISH ...
Page 807: ...Notes ENGLISH ...
Page 809: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 810: ......
Page 811: ......
Page 812: ......
Page 861: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Page 862: ......
Page 863: ......
Page 864: ......
Page 865: ......
Page 866: ......
Page 867: ......
Page 868: ......
Page 869: ......
Page 870: ......
Page 871: ......
Page 872: ......
Page 873: ......
Page 874: ......
Page 875: ......