Chapter 5: Installing the Power Supply
2. Remove the pre-installed cable gland (31), circled in red.
Figure 5-10
Removing the cable gland
31
Cable gland
3. Replace the removed cable gland (31) with an outdoor rated conduit fitting.
4. Run outdoor rated #14-12 AWG cable through the conduit fitting to the rail components at
connection points as shown in
Figure 5-9, page 35
.
5. Connect the outdoor rated cable to a circuit protected by a 250V, 4A circuit breaker.
Installing the Relay
WARNING
Only a certified electrician can complete the power supply installation. Make sure all
power sources are disconnected before performing any maintenance or service.
Always follow all national and local electrical and safety regulation for your area.
NOTE:
The Fan Control Module has no manual shut off for fan control. When wiring relays, ensure that a
manual fan shut off is installed, independent from the GrainVue system.
1. Drill a hole (35) matching the size and location specified in the image below (dimensions in mm).
2. Install an outdoor rated conduit fitting in the hole that was created in the previous step.
Figure 5-11
Installing the outdoor rated conduit fitting
35
Field drill hole
36
PNEG-2347
Cable Monitoring System
Summary of Contents for GrainVue
Page 1: ...Cable Monitoring System Installation Manual PNEG 2347 Version 1 0 Date 11 01 21 PNEG 2347...
Page 4: ...NOTES 4 PNEG 2347 Cable Monitoring System...
Page 22: ...NOTES 22 PNEG 2347 Cable Monitoring System...
Page 28: ...NOTES 28 PNEG 2347 Cable Monitoring System...
Page 42: ...NOTES 42 PNEG 2347 Cable Monitoring System...
Page 50: ...NOTES 50 PNEG 2347 Cable Monitoring System...