Chapter 6: Connecting the T/RH Cables
2. Single Connector T/RH Extension Cables need to be stripped for connection to the Mux Box, as per
the specifications in
.
Figure 6-6
Stripping specification for T/RH cables
3. Connect the T/RH cables installed in the bin to the Mux Box (24), using the stripped Single
Connector T/RH Extension Cables (25). Terminate the stripped ends of the extension cables (25)
into the Mux Box (24) using the labeled “+” and “-” ports. See
for an example of
an extension cable (25) terminated into the Cable #1 port of the Mux Box (24).
NOTE:
Make sure to secure the extension cables (25) every 3' by using P-clips.
Figure 6-7
Connecting T/RH cables to the Mux Box
24
Mux Box
25
Single Connector T/RH Extension Cables
PNEG-2347
Cable Monitoring System
47