English (GB)
24
Digital output / Relay output
Digital input - S4/S5 JP1:2 and JP5:6 set
Digital input - S4/S5 JP1:2 and JP5:6 not set
Flow switch input
Cleaning output
Response time
[ms]
<1
<1
Drift over full temperature range
+30 µA to +0 µA at 10mA
+30 µA to +0 µA at 10mA
Uncertainty [uA]
<30
<30
Description
Units
D-320-GF1-230
D-320-GF3-230
Description
D-320-GF1-230
D-320-GF3-230
Number of NO relays
2
2
Number of NO/NC relays
(error relays)
1
1
Connection
Terminal block, stripped wire, AWG 28-12
Terminal block, stripped wire, AWG 28-12
Maximal RMS current
[A]
<6
<6
Maximal working voltage
[VAC]
<240
<240
Maximal switchable load
[A]
<6
<6
Maximal number of operating
cycles
[VA]
<600
<600
Required external protection
Depending on load additional snubber circuits
might be required.
Depending on load additional snubber circuits
might be required.
Description
D-320-GF1-230
D-320-GF3-230
Number of inputs
2
2
Connection
Terminal block, stripped wire, AWG 28-12
Terminal block, stripped wire, AWG 28-12
Intended use
Digital input for external mechanical relay/
switch
Digital input for external mechanical relay/
switch
Galvanic isolation
[kV]
none
none
Maximum input frequency
[Hz]
100
100
Low input voltage
[V]
<7
<7
High input voltage
[V]
>8
>8
Input resistance
[Ohm]
>1000
>1000
Description
D-320-GF1-230
D-320-GF3-230
Number of inputs
2
2
Connection
Terminal block, stripped wire, AWG 28-12
Terminal block, stripped wire, AWG 28-12
Intended use
Digital input for external voltage output
Digital input for external voltage output
Galvanic isolation
[kV]
1 kV to system ground/earth
1 kV to system ground/earth
Maximum input frequency
[Hz]
100
100
High input
[Ohm]
>2000
>2000
Low input
[Ohm]
<100
<100
Description
D-320-GF1-230
D-320-GF3-230
Number of inputs
1
1
Connection
Terminal block, stripped wire, AWG 28-12
Terminal block, stripped wire, AWG 28-12
Intended use
For use with s::can flow detector
For use with s::can flow detector
Description
D-320-GF1-230
D-320-GF3-230
Number of outputs
1
1
Connection
Terminal block, stripped wire,
AWG 28-12
Terminal block, stripped wire,
AWG 28-12
Intended use
For use with s::can cleaning valve B-44 or flow-
cell autobrush F-446-2/F-446-1
For use with s::can cleaning valve B-44 or flow-
cell autobrush F-446-2/F-446-1