44
Unit Installation
Unit 1~16
W
hen multiple modules have direct control over one water pump, its
AC contactor is
w
ired to an AC contactor (KM1 or KM2) of any one module.
5
KM1
Unit 1
Unit 2
Unit 3
When one auxiliary electric heater serves more than one modules, its wiring terminals
11 and 12 are connected to terminals G and H respectively of an AC contactor marked
with
KM3.
11
12
11
12
11
12
11
12
G
H
KM3
11
When multiple modules have direct control over one auxiliary electric heater, its AC
c
ontactor is wired to an
AC contactor (KM3 or KM4) of any one module.
12
KM3
Unit 1~16