47
Unit Installation
3.5.3 Specification of power supply
See the table below for selection of the power lines and the air switches.
Model
Power supply
Min. sectional area of the
power cable (mm
2
)
Capacity of the
air switch (A)
Live
line
Neutral
line
ground
line
LSQWRF35VM/NaA-M 380V–415VAC 3Ph 50Hz
6
6
6
32
LSQWRF60VM/NaA-M 380V–415VAC 3Ph 50Hz
16
16
16
63
LSQWRF65VM/NaA-M 380V–415VAC 3Ph 50Hz
16
16
16
63
LSQWRF35VM/NhA-M 380V–415VAC 3Ph 50Hz
6
6
6
32
LSQWRF60VM/NhA-M 380V–415VAC 3Ph 50Hz
16
16
16
63
LSQWRF130VM/NhA-M 380V–415VAC 3Ph 50Hz
35
16
16
150
Notes:
(a)
The specifications of the breaker and power cable listed in the table above are determined based on
the maximum power
(maximum amps) of the unit.
(b)
The specifications of the power cable listed in the table above are applied to the conduit-guarded
multi-wire copper cable (like, JYV copper cable, consisting of PV insulated wires and a PVC cable
jacket) used at 45°C and resistible to 90°C (subject to GB/T16895.15-2002). If the working condition
changes, they should be modified according to the related applicable standard.
(c)
The specifications of the breaker listed in the table above are applied to the breaker with the working
temperature at 40°C. If the working condition changes, they should be modified according to the
related applicable standard.
3.5.4 Wiring of the electric control cabinet
(1) LSQWRF35VM/NaA-M, LSQWRF60VM/NaA-M, LSQWRF65VM/NaA-M, LSQWRF35VM/NhA-M
1. If the unit is a heat pump chiller with an
auxiliary electric heater, it is required to
do wiring in accordance with this diagram.
2. If the unit is capable of cooling only, the
way of wiring and elements inside the dotted
line above are not needed.
Summary of Contents for LSQWRF35VM/NaA-M
Page 5: ...1 Product Product...
Page 18: ...14 Unit Control Unit Control...
Page 29: ...25 Unit Installation Unit Installation...
Page 58: ...54 Unit Installation 3 5 7 Electric wiring digram 1 LSQWRF35VM NaA M...
Page 59: ...55 Unit Installation 2 LSQWRF60VM NaA M LSQWRF65VM NaA M...
Page 60: ...56 Unit Installation 3 LSQWRF35VM NhA M...
Page 61: ...57 Unit Installation 4 LSQWRF60VM NhA M...
Page 62: ...58 Unit Installation 5 LSQWRF130VM NhA M...
Page 63: ...59 Unit Installation...
Page 64: ...60 Unit Installation The electric wiring diagrams on the unit always prevail...