Gree GMV6 DC Inverter VRF Units Service Manual
23
After 30s of display, the automatic display is as follows; if press SW3 button within 30s, the display
is as follows. The unit automatically enters the next step of debugging:
—
Debugging code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
03_module quantity
confirmation
db
ON
03
OC
OC
ON
Note: It is important to confirm that the number of online outdoor unit modules is the same as that of
actual modules; otherwise it will need to conduct the inspection and debugging again.
Step 7:
When the unit is running to step 04, the number of online connected indoor unit is displayed.
At this time, the main board of each module is displayed as below:
—
Debugging code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
04_indoor unit
quantity confirmation
db
ON
04
ON
The quantity
of online
indoor units
Flash
After 30s of display, the display is as follows; if press SW3 button within 30s, the display is as follows.
The unit automatically enters the next step of debugging:
—
Debugging code
Progress code
Status code
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
04_indoor unit
quantity confirmation
db
ON
04
ON
OC
ON
Note: It is important to confirm that the number of online indoor unit modules is the same as that of
actual connected indoor units for the project; otherwise it will need to conduct the inspection and
debugging again.
Step 8:
Step 05 of the unit debugging is “detect internal communication”.
If there is no abnormality in the detection, the display is below, and then it automatically enters the
next step of detection.
—
Debugging code
Progress code
Status code
Meaning
Progress
LED1
LED2
LED3
Code
Display
status
Code
Display
status
Code
Display
status
05_detect
internal
communication
db
ON
05
ON
OC
ON
Once the system
inspection is
completed, it will enter
into the next step
automatically.
If an abnormality is detected, it will stay in the current state and manual troubleshooting is required.
The corresponding faults are as below: