Gree GMV6 DC Inverter VRF Units Service Manual
53
LED1
LED2
LED3
Function code
Display status
Current
process/mode
Display status
Current status
Display status
n4
On
10
Blinks
OC
Blinks
n4
On
09
Blinks
OC
Blinks
n4
On
08
Blinks
OC
Blinks
Step 3:
After selecting the value, press the SW3 confirm button. The master module displays as
follows:
LED1
LED2
LED3
Function code
Display status
Current
process/mode
Display status
Current status
Display status
n4
On
10
On
OC
On
n4
On
09
On
OC
On
n4
On
08
On
OC
On
If you do not press any button on the master unit in 5 minutes, the system will automatically exit the
current screen and the unit will resume displaying the current status. (During setting, press SW4 to return
to the previous process. If the setting is completed, press SW4 to resume the unit to the current normal
working status.)
4.2.3.8 n5 Indoor Unit Engineering SN Offset
Introduction:
When different refrigerating systems are controlled in a centralized manner (by remote monitoring or
a centralized controller), this function sets the engineering numbers of indoor units and avoids their
conflict among different systems, and therefore must be set.
Set this function only in the master system, whose centralized control address SA2 is "0000×". For
details, see the settings in section "Address DIP Switch for Centralized Control (SA2_Addr-CC)".
Setting steps:
Step 1:
Enter n5 indoor unit engineering SN offset, and ensure that the master unit displays as
follows:
LED1
LED2
LED3
Function code
Display status
Current
process/mode
Display status
Current status
Display status
n5
On
00
Blinks
00
Blinks
Step 2:
Press the SW3 confirm button to send the engineering number offset instruction. The master
module displays as follows:
LED1
LED2
LED3
Function code
Display status
Current
process/mode
Display status
Current status
Display status
n5
On
00
On
OC
On
After 10s, the system exits the mode and enters normal working.
4.2.3.9 1G Outdoor static pressure setting
Each basic module can be set separately or uniformly by the master module.