Gree GMV6 DC Inverter VRF Units Service Manual
97
2.41 "CC" No Master Units Fault
Fault display:
main board of outdoor unit, wired controller of indoor unit and receiver of indoor unit
display
Fault diagnosis:
The main board detects the master DIP switch (SA8) and determines whether it is the master.
When no master unit is detected in the multi-module communication network, the fault is generated.
Possible causes:
■ The master DIP switch is abnormal and no master unit exists in the network;
■ The communication cables are abnormal, causing the master unit to be disconnected;
■ Abnormal
detection circuit.
Troubleshooting:
No
Yes
"CC" No Master Units Fault
Make sure that only one master
unit exists in the network. After
redialing, power on the redialed
modules again
No
Properly connect the
communication cable and make
sure that it is in the same
network with other modules
The main control board
may be abnormal
Yes
Replace the main control
board
Yes
Whether DIP switch is
dialed properly for the master unit (SA8)
among all the modules
in the network?
Whether the
communication cables
for the modules of the master unit by
dialing are connected
properly ?
2.42 "CE" Mode exchanger and IDU communication error
Error display:
mode exchanger main board will display
Applicable model:
all mode exchangers
Error judgment condition and method:
For the mode exchanger, no IDU communication is detected in 1 consecutive minute.
Possible reasons:
■
Poor contact between mode exchanger main control board and IDU main control board terminal
■
Communication cord is abnormal
■
Circuit is abnormal
Troubleshooting: