Gree GMV6 DC Inverter VRF Units Service Manual
58
4.2.3.13 CA Module Failure Emergency Operation
This function is after-sales emergency setting when a module works abnormally. It shields the
abnormal module in a short time to ensure the emergency operation of other modules.
Setting steps:
Enter the function setting on the main board of the faulty basic module. The module displays as
follows:
LED1
LED2
LED3
Function code
Display status
Current process
Display status
Current status
Display status
CA
On
00
Blinks
OC
Blinks
Press the SW1 up button and the SW2 down button to select the corresponding module to enter and
exit emergency operation status.
LED1
LED2
LED3
Description
Function
code
Display
status
Current
process
Display
status
Current
status
Display
status
CA
On
00
Blinks
OC
Blinks
All basic modules run normally.
CA
On
01
Blinks
OC
Blinks
The operation of module 1 is
shielded.
CA
On
02
Blinks
OC
Blinks
The operation of module 2 is
shielded.
CA
On
03
Blinks
OC
Blinks
The operation of module 3 is
shielded.
CA
On
04
Blinks
OC
Blinks
The operation of module 4 is
shielded.
After selecting the corresponding value, press the SW3 confirm button. The shielded module displays
as follows:
LED1
LED2
LED3
Function code
Display status
Mode
Display status
Current status
Display status
CA
On
00
On
OC
On
CA
On
01
On
OC
On
CA
On
02
On
OC
On
CA
On
03
On
OC
On
CA
On
04
On
OC
On
Modules not shielded display as follows:
LED1
LED2
LED3
Function code
Display status
Mode
Display status
Current status
Display status
CA
On
00
On
OC
On
Press the SW4 back button. Modules not shielded display normal working status, and the shielded
module displays as follows:
LED1
LED2
LED3
Module
address
Display status
Module failure/indoor unit
failure
Display status Module status Display status
ADD
On
CA
On
OF
On
①
This function is valid only in systems with two or more modules connected in parallel;
②
A system can set only one module to emergency mode;