Gree GMV6 DC Inverter VRF Units Service Manual
65
faults of the outdoor unit.
4.2.4.2 n7 Parameter Query
Press the SW1 up button and the SW2 down button to select parameter query. The master unit
displays as follows:
LED1
LED2
LED3
Function Code
Display status
Current process/mode
Display status
Current status
Display status
n7
Blinks
00
Blinks
00
Blinks
Press the SW3 confirm button on the master unit to confirm the selection.
Introduction:
This function is used to query running parameters of each module of the outdoor unit in real time.
Operations:
In parameter query status, the master unit displays as follows:
LED1
LED2
LED3
Function Code
Display status
Module address
Display status
Current status
Display status
n7
On
01
Blinks
00
Blinks
n7
On
02
Blinks
00
Blinks
n7
On
03
Blinks
00
Blinks
n7
On
04
Blinks
00
Blinks
Press the SW1 up button and the SW2 down button to select the corresponding query module, and
press the SW3 confirm button. The unit displays as follows:
LED1
LED2
LED3
Function Code
Display status
Parameter code
Display status
Current status
Display status
n7
On
XX
On
Value
Blinks
LED2 displays the module parameter code, and LED3 displays the specific value. The parameters
and display sequence are listed below. "Outdoor ambient temperature (master module)" is displayed by
default. Press the SW1 up button and the SW2 down button to select the corresponding query parameter
value.
Parameter Code
Parameter Name
Remarks
01
Outdoor ambient temperature
Outdoor ambient temperature of the master module
is used.
02
Operating frequency of compressor 1
—
03
Operating frequency of compressor 2
—
04
Operating frequency of the outdoor fan
Operating frequency of outdoor fan 1 is used.
05
Module high pressure
Temperature value corresponding to the pressure
06
Module low pressure
Temperature value corresponding to the pressure
07
Discharge temperature of compressor 1
The air discharge pipe temperature is used.
08
Discharge temperature of compressor 2
The air discharge pipe temperature is used.
09
Discharge temperature of compressor 3
—
10
Discharge temperature of compressor 4
—
11
Discharge temperature of compressor 5
—
12
Discharge temperature of compressor 6
—
13
Operating frequency of compressor 3
—
14
Current of compressor 1
The integer value is used, and the wired controller
does not query.
15
Current of compressor 2
The integer value is used, and the wired controller
does not query.