Use this screen to set the maximum, target, and
minimum force/fluid pressure for a selected pump
and profile. In force/pressure mode, you can set
a target force/fluid pressure. In flow mode, you
can set a maximum force/fluid pressure. In either
force/pressure or flow mode, you can set a minimum
pressure. See

Setup Screen 4, page 14

to specify

how the system will respond if the pump begins to
operate outside of the set boundaries.

Figure 12 Setup Screen 2

Setup

Setup

Setup Screen

Screen

Screen 2

2

2 Key

Key

Key

For systems with multiple pumps and
one display, select the pump (1 to 8)
from the menu.
NOTE: Three phase systems do not
support multiple pumps.

Select the profile (1 to 4) from the menu.

In flow mode, set the maximum pump
fluid force/pressure, as a percentage of
the maximum pressure of your pump.
This field is not used in pressure mode.
NOTE: If the profile does not have a
maximum pressure setting, the motor will
not run and error code WSCX appears.

In force/pressure mode, set the force/fluid
pressure target as a percentage of the
maximum pressure of your pump. This
field is not used in flow mode.
NOTE: If closed loop pressure is
enabled, the target pressure is displayed
as a pressure value (psi, bar, MPa) rather
than a percentage of maximum pressure.
See

Setup Screens 8 and 9, page 16

to

enable closed loop pressure control.

Optionally, set a minimum pump
force/fluid pressure, as a percentage of
the maximum force/fluid pressure of your
pump.

This softkey is disabled by default, and
only appears if the Profile

Profile

Profile Lock

Lock

Lock box is

checked on

Setup Screen 22, page 22

.

Press to activate the profile that you just
edited.

Setup

Setup

Setup Screen

Screen

Screen 3

3

3

Use this screen to set your flow rate settings for a
selected pump and profile. In pressure mode, you
will set a maximum flow rate. In flow mode, you will
set a target flow rate. In either pressure or flow mode,
a minimum flow rate may be set. See Setup Screen
4 to specify how the system will respond if the pump
begins to operate outside of the set boundaries.

NOTE:

NOTE:

NOTE: With flow rate units of cc/min, the maximum
value that can be displayed is 9999. If the field
displays ####, the saved value is out of range. Go
to

Setup Screen 15, page 18

and change the flow

rate to a larger unit. Return to this screen and reduce
the setting to a lower value that will be within the
display’s range, then reset the flow rate units to
cc/min.

Figure 13 Setup Screen 3

Setup

Setup

Setup Screen

Screen

Screen 3

3

3 Key

Key

Key

For systems with multiple pumps and
one display, select the pump (1 to 8)
from the menu.
NOTE: Three phase systems do not
support multiple pumps.

Select the profile (1 to 4) from the menu.

In flow mode, set a target flow rate. This
field is not used in pressure mode.

In pressure mode, set the maximum flow
rate. The software calculates the number
of pump cycles needed to achieve that
flow rate. This field is not used in flow
mode.
NOTE: If the profile does not have a
maximum flow rate setting, the motor will
not run and error code WSC_ appears.

Optionally, set a minimum flow rate.

This softkey is disabled by default, and
only appears if the Profile

Profile

Profile Lock

Lock

Lock box is

checked on

Setup Screen 22, page 22

.

Press to activate the profile that you just
edited.

3A2527H

13

Summary of Contents for E-Flo 17V232

Page 1: ...rofessional professional professional use use use only only only Important Important Important Safety Safety Safety Instructions Instructions Instructions Read all warnings and instructions in this ma...

Page 2: ...1 12 Setup Screen 2 13 Setup Screen 3 13 Setup Screen 4 14 Setup Screen 5 15 Setup Screen 6 15 Setup Screen 7 16 Setup Screens 8 and 9 16 Setup Screens 10 and 11 17 Setup Screens 12 and 13 17 Setup Sc...

Page 3: ...anual for Advanced Display Control Module ADCM 3A0539 Instructions Parts Manual 4 Ball Lowers 334359 Instructions Parts Manual E Flo DC 2000 3000 and 4000 Circulation Pumps 3A4030 Instructions Intelli...

Page 4: ...models only install the jumper connector 5 over the top two terminals of the motor using the screw 5a Three phase models do not have a jumper connector NOTE NOTE NOTE To connect up to 8 motors togethe...

Page 5: ...ale 25 ft 8 m Table Table Table 2 2 2 ADCM ADCM ADCM Cable Cable Cable Connections Connections Connections ADCM ADCM ADCM Port Port Port Number Number Number Connector Connector Connector Purpose Purp...

Page 6: ...Figure 4 is a view of the control module display and keys Table 2 explains the function of the membrane keys on the control module As you move through the screens you will notice that most information...

Page 7: ...iting Up Down Up Down Up Down Arrows Arrows Arrows Move between screens or fields on a screen or to increase or decrease the numeric values in a field that can be edited Enter Enter Enter Press to act...

Page 8: ...Use the up and down arrow keys to change the number Press the right arrow key to move to the next digit When all digits are correct press the right arrow key again to accept Check Check Check Box Box...

Page 9: ...from the menu to stop the pump Displays the current pump speed in cycles per minute Displays the current pump pressure as a percentage If a transducer is used this icon is replaced by the pressure ico...

Page 10: ...Setup Screen 4 page 14 to set or disable the pressure alarms Run Run Run Screen Screen Screen 4 4 4 This screen displays fluid flow settings for the active pump and profile Fluid flow can be measures...

Page 11: ...e 18 Figure 9 Run Screen 5 Run Run Run Screens Screens Screens 6 9 6 9 6 9 and and and 10 13 10 13 10 13 Run Screens 6 9 single or x2 parent pump and 10 13 x2 child pump display a log of the last 20 a...

Page 12: ...lect the operating mode force pressure or flow from the menu In force pressure mode the motor adjusts the pump speed to maintain the fluid pressure percentage set on Setup Screen 2 If the flow limit i...

Page 13: ...he Profile Profile Profile Lock Lock Lock box is checked on Setup Screen 22 page 22 Press to activate the profile that you just edited Setup Setup Setup Screen Screen Screen 3 3 3 Use this screen to s...

Page 14: ...Deviation Deviation or Alarm Alarm Alarm For runaway control set the maximum flow to Alarm Alarm Alarm If the flow rate exceeds the maximum entered on Setup Screen 3 for five seconds an alarm symbol a...

Page 15: ...mode Use the arrow keys to move the motor or pump shaft up or down Select the correct pump lower size from the menu The default is blank If custom is selected a field opens for you to input the size...

Page 16: ...are identical except Screen 8 is for transducer 1 and Screen 9 is for transducer 2 Selecting a transducer and a pump activates closed loop pressure control NOTE NOTE NOTE Closed loop pressure control...

Page 17: ...other pump up one position For example if AD00001 is changed to be pump 4 AD00002 will become pump 1 AD00003 will become pump 2 and so on Figure 19 Setup Screens 10 and 11 Screen 10 shown Setup Setup...

Page 18: ...l port baud rate from the menu This is a system wide setting 38400 kbps 57600 kbps default 115200 kbps Setup Setup Setup Screen Screen Screen 15 15 15 Use this screen to configure and control the tank...

Page 19: ...isor Module is required for this function Configures Port 4 pin 4 as an output to allow for the connected device to receive an alarm when the level of the Primary Tank is above the value that is defin...

Page 20: ...mA supply Set the numerical values for the scaling ceiling for 4 20mA signal Setup Setup Setup Screen Screen Screen 18 18 18 This screen is for enabling a modbus communications alarm and disabling the...

Page 21: ...p switch when going from profile 0 stopped to run before the pump can start When the run stop switch is active the following pop up appears Enable or disable auto restart The default setting is disabl...

Page 22: ...l pumps connected to the display All pumps attached to the display must not be pumping material when the software update is initiated Figure 28 Setup Screen 21 Setup Setup Setup Screen Screen Screen 1...

Page 23: ...Description None Basic 6 Alarm The Mode Select knob is set between Pressure and Flow Set the knob to the mode you want None Basic and Advanced 9 None A blink code of 9 is not an error code but an ind...

Page 24: ..._ K1D_ Advanced 1 2 Alarm Flow is below minimum limit K2D_ K2D_ K2D_ Advanced None Deviation Flow is below minimum limit K3D_ K3D_ K3D_ Advanced None Deviation Flow exceeds maximum target also indicat...

Page 25: ...below 85 C 185 F internally T4D_ T4D_ T4D_ Basic and Advanced 4 6 Alarm Motor over temperature Motor will throttle itself to stay below 85 C 185 F internally V1I_ V1I_ V1I_ Basic and Advanced 2 Alarm...

Page 26: ...Code Code Code Alarm Alarm Alarm or or or Deviation Deviation Deviation Description Description Description WSD_ WSD_ WSD_ Advanced 1 5 Alarm Invalid lower size occurs if the unit is operated before...

Page 27: ...shipped loose 1 5 24N910 CONNECTOR jumper includes item 5a 1 5a SCREW cap socket head M5 x 40 mm 1 6 24P823 BRACKET KIT control module includes items 6a 6f 1 Ref Ref Ref Part Part Part Description Des...

Page 28: ...a BRACKET control module 1 6b BRACKET mounting 1 6c LOCKWASHER external tooth M5 4 Ref Ref Ref Part Part Part Description Description Description Qty Qty Qty 6d WASHER M5 2 6e SCREW cap socket head M5...

Page 29: ...iary Solenoid Kit 24Z671 Tank Fill Kit 241405 24A032 Reed Switch Counter Kit 17B160 Fiber Optic Cables KM172 17T898 Fiber Optic Cables KM173 BPR BPR BPR Controller Controller Controller Kit Kit Kit 24...

Page 30: ...ead Write 16 Bit Pressure units see Table 7 403230 Actual Tank Level 1 Read Write 16 Bit Pressure units see Table 7 403231 Actual Tank Level 2 Read Write 16 Bit Pressure units see Table 7 403232 Confi...

Page 31: ...that only the registers which will be monitored and changed on a regular basis be mapped and the remaining parameters be configured with the display 404150 Pressure Minimum Read Only 16 Bit Pressure...

Page 32: ...34 47 mPa 344 74 bar 3 5 psi 34 5 kPa 0 345 bar Tank level sensor 404207 Closed Loop Enable Transducer 1 Read Write 16 Bit 404208 Closed Loop Enable Transducer 2 Read Write 16 Bit 0 Not Enabled 1 Enab...

Page 33: ...y 406104 Estimated Pump Force or Pressure Read Only 406105 Transducer 1 Pressure Read Only 0 65535 406106 Transducer 2 Pressure Read Only 0 65535 406107 ADCM Input Status Bits Read Only bit 0 bit 1 0...

Page 34: ...p 2 Alarms 2 High Word Read Only 406138 Pump 2 Alarms 2 Low Word Read Only 406139 Pump Control Bitfield Read Write bit 0 Clear Alarm bit 1 Reset Batch bit 2 Reset Maint Counter 1 bit 3 Reset Maint Cou...

Page 35: ...te 0 65535 406152 Primary Agitator High Speed Deviation Read Write 0 65535 406153 Primary Agitator Low Speed Deviation Read Write 0 65535 406154 Primary Agitator Low Speed Alarm Read Write 0 65535 406...

Page 36: ...ssure units see table 7 405x02 Pressure Force Maximum Read Write 16 Bit Pressure units see table 7 405x03 Flow Minimum Read Write 16 Bit Flow units see table 7 405x04 Flow Target Read Write 16 Bit Flo...

Page 37: ...ansducer 11 Deviation WSC_ Zero setting on active profile 12 Advisory END_ Encoder stroke range calibration in progress 13 Alarm A4N_ Over Current 14 Alarm T4D_ Over Temperature 15 Alarm WCW_ Dual low...

Page 38: ...ast 9 Advisory E5S_ X2 Calibration Error aborted 10 Advisory E5U_ X2 Calibration Error unsteady 15 Alarm CAC_ CAN Communication Display others Reserved 404116 404116 404116 Pump Pump Pump Alarm2 Alarm...

Page 39: ...rms 3 Reads 1 if there are any active deviations 4 Reads 1 if there are any active advisories 5 Setup changed 6 Reserved 7 Run Stop switch closed 8 Profile 1 changed 9 Profile 2 changed 10 Profile 3 c...

Page 40: ...er 10 10 1 0 L min Gallons min 403210 1 Flow Register 10 10 1 0 Gal min cc min 403210 2 Flow Register 1 1 cc min oz min 403210 3 Flow Register 1 1 oz min Flow Cycles min 403210 4 Flow Register 10 10 1...

Page 41: ...led from the Display Make sure the display fiber optics communication gateway and PLC are connected properly Refer to Communication KIt manual Use Setup Screen 12 to enable remote control and set your...

Page 42: ...t up for a pressure transducer on Setup Screen 8 but no transducer is detected It will show on bit 1 of register 404114 6 Monitor Monitor Monitor pump pump pump cycle cycle cycle rate rate rate flow f...

Page 43: ...of the pump Viscosity changes throughout time can increase the back pressure in the line such that when it is time to switch from flow mode off production to pressure mode the pump will not move beca...

Page 44: ...Graco distributor Connections for Local Control Single display and 1 or more pumps in a chain Communication Equivalent C P3 P2 P1 D P1 P2 P3 P n P 1 C J P 1 P 2 P 3 P n D D Display C CAN cable P Pump...

Page 45: ...isplay P Pump number P n Last pump maximum allowed in a chain 8 J Jumper S Run Stop switch F Fiber optic cable C CAN cable Cable plug on device see Cable Connection page 5 Loss of remote communication...

Page 46: ...U E FOCM Fiber Optic Converter Module 24R086 G Graco Gateway D Display number D n Last display P Pump number P n Last pump maximum allowed in a chain 8 J Jumper S Run Stop switch F Fiber optic cable C...

Page 47: ...4R086 Fiber Optic Converter Module contains one fiber optic connection module configuring the FOCM for additional displays will require purchase of up to 3 additional fiber optic connection modules M...

Page 48: ...g flashing red light No harm can be done by attempting to program the module multiple times 1 Remove power from the Graco Control Module by turning off system power NOTE NOTE NOTE Alternately software...

Page 49: ...date successful Update unsuccessful Update complete no change necessary 9 Press to continue If the token is still inserted the remote loading procedure will begin anew Return to step 5 for step progre...

Page 50: ...WARRANTY WARRANTY WARRANTY AND AND AND DISCLAIMS DISCLAIMS DISCLAIMS ALL ALL ALL IMPLIED IMPLIED IMPLIED WARRANTIES WARRANTIES WARRANTIES OF OF OF MERCHANTABILITY MERCHANTABILITY MERCHANTABILITY AND...

Reviews: