GMC-I Messtechnik GmbH
R2500–8
Mechanical Installation / Preparation
Figure 1: Housing Dimensions and Panel Cutout
The R2500 controller is intended for installation to a control panel. The
installation location should be vibration-free to the greatest possible
extent. Aggressive vapors shorten the service life of the controller.
Requirements set forth in VDE 0100 must be observed during the
performance of all work. Work on the device may only be carried out by
trained personnel who are familiar with the dangers involved.
Set the housing into the panel cutout from the front, and secure it from
behind at the top and bottom with the two included snap retainers.
Several devices can be mounted next to each other without separators at
the side.
In general, unobstructed air circulation must be assured when one or
several devices are installed. The ambient temperature underneath the
devices may not exceed 50
C.
In order to assure IP 67 protection, an appropriate seal must be installed
between the device and the panel.
Electrical Connection
Figure 2: Connector Terminal Positions
48
48
45
+0.6
45
+0.6
104
119
5
12
12
14
15
15
16
17
18
19
20
1
2
3
4
5
6
7
8
9
10
Connectors: screw terminals for wire with 1.5 square mm cross-section
or two-core wire-end ferrules for 2
0.75 square mm