GMC-I Messtechnik GmbH
R2500–30
hLt.X
The running program has been halted, the momentary setpoint has been frozen (X stands for the current segment).
The program can be halted with a binary input:
In1 = PhLt
.
Control tracks
Two control tracks can be activated for the duration of the segments. They can be assigned to available switching outputs with
the setting:
Out... = tr...
The states
run
and
hLt
can also be assigned to available switching outputs with the settings:
Out... = Prun
and
Out... = PhLt
.
Control parameters
When the program controller is active, the control parameters should not (cannot) be set manually or by means of
self-tuning, because a constant setpoint is required for usable optimization results.
Select
ProG = diS
to this end.
Display
The displays are supplemented as follows at the operating level:
The momentary setpoint appears at the
setpoint display
when a program is running, and only dashes appear after the
program has been ended because there is no longer an active setpoint. The setpoint cannot be changed.
A
status display
also appears. Current status, namely
StoP
,
run.X
,
Wt.X
or
hLt.X
(X stands for the current segment), appears
at the bottom display.
Operation
The sequence can be controlled in the status display with the help of the up and down scroll keys, if it has not been configured
to binary inputs.
In order to avoid erroneous settings, changes must be acknowledged within 5 seconds with the
key.
The change can be discarded by pressing the
key.