Technical Data
Refer to the data sheet for complete technical data (3-349-377-03).
Ambient Conditions
Annual mean relative humidity, no condensation
75%
Ambient temperature
Nominal range of use
Operating range
Storage range
0
C ... + 50
C
0
C ... + 50
C
–25
C ... + 70
C
Auxiliary Voltage
Nominal Range of Use
Power Consumption
Nominal Value
Voltage
Frequency
110 V AC
230 V AC
85 to 265 V AC
48 to 62 Hz
Typically 1.5 W
24 V DC
20 to 30 V DC
–
Relay output
Floating NO contact, common phase for switching
outputs A1 and A2
Switching capacity
250 V AC/DC, 2 A, 500 VA / 50 W
Service life
> 5
10
5
switching cycles at nominal load
Interference suppression
Utilize external RC element (100
- 47 nF) at
contactor
Electrical Safety
Safety class
II, panel-mount device per DIN EN 61010-1, section 6.5.4
Fouling factor
2, per DIN EN 61010-1, section 3.7.3.1 and IEC 664
Measuring category
II, per DIN EN 61010 appendix J and IEC 664
Operating voltage
300 V per DIN EN 61010
EMC interference emission
EN 61326
EMC interference immunity
EN 61326