GMC-I Messtechnik GmbH
R2500–13
Automatic Operation / Off
Manual / Automatic Selection
Actual
Off
– No alarm function
– No indication of errors
Operating Level
The controller can be deactivated by pressing and holding the
key, if it
is configured to on/off.
Man. Factor
Actual
Manual Operation
Operating Level
– Alarm function and error indication identical to automatic operating mode.
– The actuator outputs are controlled with the scroll keys and not by the controller function.
– Switching between manual and automatic modes is bumpless in both directions.
– PDPI controller: The manipulating factor is displayed as a percentage. Value
changes are forwarded immediately to the control outputs.
– Step-action
controller:
The switching outputs can be adjusted directly with “more” or
“less” by pressing the up and down scroll keys.
If the
key is configured to
manual / automatic
Summary of Contents for R2500