GMC-I Messtechnik GmbH
R2500–28
Maximum setpoint
sp H
SP L
... X2
X2
Limiting the setpoint entry
Minimum setpoint
SP L
X1 ...
SP H
X1
Maximum manipulating factor
y H
–100 ... 100%
100%
Minimum manipulating factor
y l
–100 ... 100%
–100%
Actual value correction
Cal
–MRS/2 ... +MRS/2
0
Not with standard signal
Actual gain value
gain
0 ... 500%
100%
Decimal point position
dpnt
0, 0.1, 0.02, 0.003
0
With standard signal only
Upper range limit, standard signal
rn h
r n L
... 9999
100
Lower range limit, standard signal
rn l
–1999 ...
r n H
0
Manip. factor for actuation mode
y st
–100 ... 100%
0
Manip. factor for feed-forward control
y ff
–100 ... 100%
0
See page 26
Sensor error manipulating factor
y se
–100 ... 100%
0
See page 43
Actuation setpoint
spsv
SP L
...
SP H
0
For hot-runner controllers only, see pages 25
and 26
Start-up manipulating factor
y sv
–100 ... 100%
10
Dwell time
t sv
0 ... 300 s
0
Boosting (setpoint increase)
spbo
0 ... MRS/2
0
Boosting time
t bo
0 ... 600 s
0
Oscillation inhibiting
tsvp
oFF, 0.3 ... 25 s
oFF
See page 23
Parameters
Display
Range
Standard
Comments