Remedies
Error Acknowledgement
Errors are acknowledged by pressing the
key and acknowledging the
Quit AL
display within 5 seconds with the
key.
loop error
Measured temperature rise is too small
with heat on at 100%
Control outputs inactive, error message remains until
acknowledged (see below).
4
parameter error
Parameter not within permissible limits
Control outputs inactive, the parameter level is disabled.
5
digital error
Error detected by digital component
monitoring
Control outputs inactive
6
analog error
Hardware error detected by analog
component monitoring
Control outputs inactive
6
Display
Error Message Source
Response
Remedy
1. Eliminate sensor error.
2. Inspect current transformer.
3. Avoid disturbances which impair the self-tuning sequence, e.g. sensor
errors.
4. Close the control loop: Check the sensor, the actuators and the heater for
correct functioning. Check sensor-heater assignments (wiring). Correctly
optimize control parameters
tu
and
Pb I
.
5. Restore default configuration and default parameters, and then
reconfigure or load user-defined default settings.
6. Arrange for repair at authorized service center.