GMC-I Messtechnik GmbH
R2500–47
Replacing an R2400 Controller with an R2500 Controller
Replacement with regard to feature A
•
When configured as a step-action controller (R2400, features A2, A4), the configuration of the corresponding output is not Outx = CooL in the
case of the R2500, but rather Outx = HcLo.
R2400
R2500
Feature
Heating output
Cooling output
Feature
Configuration
A1
Transistor
—
A1
Out1 = HEAt
Out2 = oFF
A1
Relay
—
A2
Out1 = HEAt
Out2 = oFF
A1
—
Transistor
A1
Out1 = CooL
Out2 = oFF
A1
—
Relay
A2
Out1 = CooL
Out2 = oFF
A2, A4
Transistor
Transistor
A1
Out1 = HEAt
Out2 = CooL
A2, A4
Relay
Transistor
A2
Out1 = HEAt
Out2 = CooL
A2, A4
Transistor
Relay
A2
Out1 = CooL
Out2 = HEAt
Rewiring:
3 to 4 and 17 to 15
A2, A4
Relay
Relay
A2
Out1 = HEAt
Out2 = CooL
Out = XCh
Rewiring:
15 to 20
16 to 19
17 to 18
19 to 16
20 to 15
A3
Continuous
—
A5
Out1 = oFF
Cont = HEAt
A3
—
Continuous
A5
Out1 = oFF
Cont = CooL
A3
Continuous
Relay
A5
Out1 = CooL
Cont = HEAt
Rewiring:
17 to 15
A3
Relay
—
A5
Out1 = HEAt
Cont = Proc
A3
—
Relay
A5
Out1 = CooL
Cont = Proc
A3
Relay
Relay
A5
Out1 = HEAt
Out2 = CooL
Out = XCh
Rewiring:
15 to 20
16 to 19
17 to 18
19 to 16
20 to 15
Summary of Contents for R2500