9.1.5.1 SETTING THE HEATING CURVE FOR THE FIRST HEATING CIRCUIT
Heating curve is set on page 3 of the “Heating/Cooling Circuit 1” menu!
PAGE 3
Tsh
– Space heating temp.; T(Ta) – Ambient temp.
Ta1
Ta2
Ta3
Ta4
Ta5
Tsh1
Tsh2
Tsh3
Tsh4
Tsh5
NOTE:
It is recommended to reset only the space heating water temperatures (figure above on
the right). Resetting ambient temperatures for the heating curve affects both heating
circuits.
EXAMPLE
Example:
The customer wants the
room temperature to be 21 °C, but the heat pump heats the rooms to 22 °C. In
this case the heating curve must be lowered. On page 3, all temperatures need to be lowered by 2-
3 °C,
which means that the room temperature will be lower by 1 °C. If the room temperature is lower than the
desired temperature, the temperature values must be increased.