1.
Digital thermostat
controls the max flow temperature in case of Back-Up or Auto
–
Emergency operation. In the Back-Up and Auto
–Emergency operation, the Main
controller is still controlling the heating temperature.
Auto
– Emergency operation
Example:
If the Unit turns ON the Back-Up heaters or Emergency operation and the setting on
the Digital thermostat is set to 30°C, the heaters will work only until 30°C and then
switch OFF regardless of the demand from the main controller. If, however the Digital
thermostat is set to 60°C, the Main controller will switch OFF the heaters according to
its needs.
Manual operation
(manual emergency switch ON):
In manual operation all the circulating pumps are switched ON and the Electrical
heaters work according to the setting on the Digital thermostat, regardless of the
setting on the Main controller.
Example:
if the Manual emergency operation is ON and the temperature set on the Digital
thermostat is set to 50, the heating water will be heated to 50°C. The Circulating
pumps will run all the time.
2.
Analog thermostat
controls the max flow temperature in case of Back-Up or Auto
–
Emergency operation for DHW. In Back-Up and Auto
–Emergency operation, the Main
controller is still controlling the DHW temperature.
Auto
– Emergency operation
Example:
If the Unit turns ON the Back-Up heaters or Emergency operation for DHW and the
setting on the thermostat is set to 40°C, the heaters will work only until 40°C and then
switch OFF regardless of the demand from the main controller. If however the
thermostat is set to
60°C, the Main controller will switch OFF the heaters according to
its needs (DHW set temperature).