background image

OPERATION

JUNO-NET

Logging

Devices Under Test

Indication When a Device is Tested

Individual detector tests are not logged (they would fill the log very quickly)
Entry to Caretaker Test Mode is logged

All detectors and callpoints in all Zones will be put into test mode
Detectors and callpoints not assigned to Zones will also be put into test mode

When a detector is activated (using smoke spray for example):

The LED on the detector is activated whilst the detector is above the fire alarm threshold
The Main Panel Conventional Sounders will operate for 1 second
The Loop Sounders connected to the same sub-panel as the detector under test will sound for
1 second
The event is reported on the Main Panel and Repeater LCD displays for 15 seconds

Testing More Than One Device

Disablements

Sensor sensitivity

Other

Detectors and callpoints can only be tested one at a time. The LED must be extinguished on

the current device before moving on to test the next device. (Don't use too much smoke spray.)

All disablements for sounders, loops and detectors are ignored during Caretaker Test Mode.

However the LED on disabled detectors will not be lit when the detector is tested (all other aspects of
the test will be as normal).

This will not be changed on entry to test mode (so at night the sensitivity may be high and

during the day low - depending on the system settings).

Whilst in Caretaker Test Mode the SOUND ALARMS button will remain functional
Caretaker Test Mode can be initiated from a Main Panel or Repeater

1.9 CARETAKER TEST MODE (continued...)

11

JUNO-NET EN-54

MAINTENANCE MANUAL

21-08-2005

REVISION 1.0

OPERATION &

ss

ss

Summary of Contents for JUNO-NET EN-54

Page 1: ...OPERATION MAINTENANCE MANUAL JUNO NET Fire Alarm Control Panel EN 54 JUNO NET EN 54 MAINTENANCE MANUAL 21 08 2005 REVISION 1 0 OPERATION ss ss...

Page 2: ...2 8 Use of programming functions for maintenance 2 9 Getting into Programming Mode 2 10 Logbook 2 10 Event data sheet OPERATION 1 3 Reset the system 1 4 Sound and silence the alarms 1 5 Read the Fire...

Page 3: ...icates that at least one disablement exists If the LED is GREEN it means that the panel is in ACTIVE mode If the LED is flashing GREEN then the panel is in INSTALLATION mode If the LED is AMBER it ind...

Page 4: ...ated Press to Enable or disable all sounders on the system Both Conventional or Addressable When LED is lit all sounders are disabled Enabled if LED is off Pressing this switch disables or enables all...

Page 5: ...TUS FIRE will remain lit RED Press the INTERNAL BUZZER SILENCE to silence the Internal Buzzer It will also turn off the INTERNAL BUZZER SILENCE button LED button LED At the fire control panel the STAT...

Page 6: ...ILENCE RESOUND All sounders turn on The illuminates RED Press the The sounders turn off The extinguishes button LED button LED ALARMS SILENCE RESOUND ALARMS SILENCE RESOUND ALARMS SILENCE RESOUND 1 4...

Page 7: ...xt queued message Do this until all messages have been reviewed The LED stops flashing RED but remains lit once all messages have been displayed After 20 seconds the first fire event will be re displa...

Page 8: ...08 2005 REVISION 1 0 OPERATION ss ss FIRE FAULT PRE ALARM TEST DISABLED SYSTEM ON ALARM FAULT SUPPLY FAULT SYSTEM FAULT TRANS FAULT PAPER FEED LAMP TEST SYSTEM RESET INTERNAL BUZZER SILENCE DISABLED...

Page 9: ...1997 AC 1999 EN54 Press and hold the LAMP TEST All LEDs shown in this diagram should be illuminated All pixels on the LCD display should turn black All external Zone LEDs if fitted should be illuminat...

Page 10: ...TH 2 1997 AC 1999 EN54 4 1997 AC 1999 EN54 OPERATION JUNO NET 1 8 PERFORM A FIRE DRILL Authorized User Level Access To start the fire drill press the The following will occur All sounders turn on The...

Page 11: ...uired in order for the LCD display to show the described above format Press the QUEUE REVIEW TEST first then the CONTROLS LAMP TEST momentarily The FAULTS SYSTEM FAULT button button LED will light mom...

Page 12: ...Repeater LCD displays for 15 seconds Testing More Than One Device Disablements Sensor sensitivity Other Detectors and callpoints can only be tested one at a time The LED must be extinguished on the c...

Page 13: ...NT Re pressing the SELECTED DETECTORS button again will re enable the detectors LED LED LED button Using the programming functions see the Installation Commissioning Manual individual detectors can be...

Page 14: ...n to re enable the relays and I O modules button LED LED The QUEUE REVIEW DISABLED illuminates AMBER LED OPERATION JUNO NET 1 10 DISABLEMENTS continued 1 10 2 AUXILIARY RELAYS 1 10 3 SOUNDERS ENABLE D...

Page 15: ...e procedure described below 1 Enter either a valid User or Programming Code 2 Select Function 3 1 Zones Disable Assign using the arrow keys or the arrow keys on the either the Infrared remote control...

Page 16: ...g bracket again and re insert the mounting pin with the new roll The pointing towards the main circuit board Thread the paper into the printer Close the fascia and replace the screws Press the PAPER F...

Page 17: ...SIM CARD The SIM CARD is mounted on the back of the main board Release the by pulling in the direction of the arrows With the retaining clips held in the released position push the SIM CARD forward a...

Page 18: ...STATIC SENSITIVE DEVICES ESD TAKE SUITABLE ESD PRECAUTIONS WHEN REMOVING OR INSTALLING PRINTED CIRCUIT BOARDS ELECTRO STATIC SENSITIVE DEVICES ESD TAKE SUITABLE ESD PRECAUTIONS WHEN REMOVING OR INSTA...

Page 19: ...WITH THE MANUFACTURER S RECOMMENDATION ALWAYS USE SEALED LEAD ACID BATTERIES 18 JUNO NET EN 54 MAINTENANCE MANUAL 21 08 2005 REVISION 1 0 OPERATION ss ss 2 7 REPLACING THE ELECTRICAL MAINS FUSE On th...

Page 20: ...ter is free before starting a new print job If you wish to stop a printout enter the function again and you will be given the option of canceling the printout This function cannot be accessed remotely...

Page 21: ...ted to the Analogue Loops Note that in Installation Mode all information is live i e the count of devices will change as the panel learns and device types will be updated if they change In Active Mode...

Page 22: ...Zones you wish to put into test mode Exit programming mode but DO NOT press SYSTEM RESET as this clears all test modes In test mode when a detector is activated the LED on the detector will be illumi...

Page 23: ...tor LED can be lit at any one time Select the device and SWITCHED ON and press ENTER The device will typically take a few seconds to respond Selecting NORMAL for that device or selecting SWITCHED ON f...

Page 24: ...on B SP Backspace ESC Reject ESCape from current selection EXIT Press both keys simultaneously to stop programming SHIFT Toggle this keypad to switch from alpha numeric to numeric 2 9 GETTING INTO PRO...

Page 25: ...RINTER CONNECTOR PRINTER FUSE PS2 PC KEYBOARD ADAPTOR STANDOFFS 4 FOR LOOPCARD SIM CARD CONNECTOR QUAD UART 50 WAY BOX HEADER FOR J NET CON 16 WAY BOX HEADER FOR LOOP CONNECTOR LOOPCARD HEADER JUNO NE...

Page 26: ...0 9 are used to input numbers and are used to select items B SP and are often used to change fields move the cursor are often used to select the loop ENTER is used to select items and to store change...

Page 27: ...or sub menu use either and ENTER or 0 9 and ENTER HOME takes you to 1 Review ESC takes you up a menu level Any number presses 0 9 will append a digit to what you see unless 1 You are at the very top...

Page 28: ...mple pages of the logbook are provided here and can be photocopied to produce a logbook that conforms to EN54 14 The sample below is for the reference data e g the name of the responsible person whils...

Page 29: ...MAINTENANCE JUNO NET 2 10 EVENT DATA SHEET DATE TIME EVENT INITIALS ACTION REQUIRED DATE COMPLETED 28 JUNO NET EN 54 MAINTENANCE MANUAL 21 08 2005 REVISION 1 0 OPERATION ss ss...

Reviews: