OPERATION
JUNO-NET
1.6 ACTIVE DELAYS - (Authorized User Level Access)
During installation, via the programming functions, delays can be set for the sounders, I/O modules and
fire brigade transmission.
These delays are only active when the ACTIVE DELAYS LED is illuminated. At all other times the sounders,
I/O modules and fire brigade transmission will operate immediately a fire is detected.
To enable or disable these delays press the ACTIVE DELAYS button.
Note that it is also possible, via the programming functions, to set ACTIVE DELAYS to automatically turn off
at night.
For details on the programmable features and delays refer to the ‘Installation & Commissioning Manual’.
7
JUNO-NET EN-54
MAINTENANCE MANUAL
21-08-2005
REVISION 1.0
OPERATION &
ss
ss
FIRE
FAULT
PRE-ALARM
TEST
DISABLED
SYSTEM ON
ALARM FAULT
SUPPLY FAULT
SYSTEM FAULT
TRANS. FAULT
PAPER FEED
LAMP TEST
SYSTEM RESET
INTERNAL BUZZER
SILENCE
DISABLED
TEST
FAULT
FIRE
AUXILIARY
RELAYS
SOUNDERS
ENABLE/DISABLE
SELECTED
DETECTORS
DELAYS
ACTIVE
STATUS
FAULTS
CONTROLS
DISABLEMENTS
QUEUE REVIEW
SILENCE/RESOUND
ALARMS
ESC
OK
FIRE ALARM SYSTEM
COMPLIES WITH
-2: 1997 / AC: 1999
EN54-4: 1997 / AC: 1999
EN54
NOTE:
Some functions are only available at Authorized User level of Access. To enter this mode, a valid
user Code has to be entered using the panel's front display keypad.
The factory default code is:
To enter, press OK then press 5 consecutive
, then press OK again. If code entry was
successful, the words " USER ACCESS LEVEL" will appear on the top line of the LCD display.
Functions indicated as available to the General User do not require an access code to be entered
.