5.2. Maintenance
The only maintenance required is to periodically inspect the fans. The blades should
be free turning and built up dirt should be removed from the blades.
11
CHAPTER FIVE: TROUBLESHOOTING AND MAINTENANCE
5.1 Status Display Codes
Display
Name
Description
Possible Cause
1
EEPROM
Fault
Parameter EEPROM
checksum fault
Internal problem
8
Reset
(Flashing)
N/A
Internal problem
b
Bus Over
Voltage
DC bus exceeded
450VDC
Regenerative braking cir-
cuit not working, check
fuse in regen circuit
C
Clamp
(Disabled)
Vector drive disabled
Control is disabling the
drive
E
Encoder
Fault
Encoder fault detected
Encoder faulty or en-
coder wiring broken
H
Heatsink
Over Tem-
perature
Heatsink exceeded
65ºC
Fan(s) failed
L
LS/ECB
Motor RMS over cur-
rent
Mechanical binding in
motor or spindle
0
Normal Op-
eration
Amp enabled
Normal when rotating
S
HS/ECB
Output short circuit de-
tected
Motor windings shorting
U
Bus Under
Voltage
DC bus below 150VDC
nominal
AC input voltage to drive
is low or off
Single
segment
Normal Op-
eration
Amp enabled
Normal @ zero speed