Instruction Manual M A M - 8 7 0
Senator Industrial Air Compressors
8
PARAMETER
SET VALUE
FUNCTION
PRE-ALARM
TEMP
0105 °C
Alarm when the discharge air temperature at the air
end reaches this set value.
STOP TEMP
110 °C
Shutdown when the discharge air temperature at the
air end reaches this set value.
STOP PRESS
00.85 MPa
Shutdown when the discharge air pressure reaches
this set value.
MAX U.L.
PRESS
00.80 MPa
The UNLOAD PRES set by the user cannot exceed
this value.
#TOTAL RUN
TIME
****** H
The factory can modify the total running time. Do
not change it.
TOTAL LOAD
TIME
****** H
The factory can modify the total load time. Do not
change it.
RESET FAULT
8888
Set the password that is used to clear all of the fault
history.
CURR
UNBALANCE
0010
When the Maximum Phase Current ÷ Minimum
Phase Current is greater than 1 + (Set Value ÷ 100),
the unbalance protection will stop the machine. Set
this value greater than 15 to disable the current
unbalance function.
LACK PHASE
TIME
005.0 S
Set this value
≥ 20 S to disable the lack
-of-phase
shutdown protection function.
PRODUCT
DATE
****Y**M**D The factory inputs the production date of the unit.
Do not change it.
SERIAL
NUMBER
********
The factory inputs the serial number of the unit. Do
not change it.
#PHASE
PROTECT
ENABLE
Enable phase protection.
#SELECT FREQ
50Hz
Set the power frequency.
SEQ MODE
COMPATIBLE Set the sequencing function compatibility.
HIGH
VOLTAGE
436V
If the voltage is higher than the set value, it will
shutdown the compressor and report voltage too
high. Set this value to 0000 to disable this function.
LOWER
VOLTAGE
394V
If the voltage is lower than the set value, it will
shutdown the compressor and report voltage too low.
Set this value to 0000 to disable this function.
LOW T
PROTECT
-5
℃
If the temperature is lower than the set value, the
compressor cannot be started and reports temperature
too low.
#MAX RUN
TIME
0000 H
Set this value to “0000” to disable the maximum run
time shutdown function.
ALARM LONG
STOP
0000 H
Set this value to “0000” to disable the overdue
maintenance shutdown function.
COM SET PAR.
ENABLE
Spare parameter setting channel.
PARAMETER 1
****
Set the FACTORY SET PASSWORD.