2

Detection areas: zone 1 or zone 2

A

r

t

r

t

Zone 1

Zone 2

A

r

t

r

t

Zone 1

Zone 2

A

r

t

r

t

Zone 1

Zone 2

A

r

t

r

t

Zone 1

Zone 2

Installation height 

(A)

Walking persons

frontal (r)

Walking persons

across (t)

2.0 m

8 x 3.5 m (28 m

2

)

8 x 3.5 m (28 m

2

)

2.5 m

9 x 4 m (36 m

2

)

11 x 4 m (44 m

2

)

3.0 m

10 x 4.5 m (45 m

2

)

15 x 4.5 m (68 m

2

)

3.5 m

10 x 5 m (50 m

2

)

15 x 5 m (75 m

2

)

4.0 m

10 x 5 m (50 m

2

)

15 x 5 m (75 m

2

)

4.5 m

10 x 5 m (50 m

2

)

15 x 5 m (75 m

2

)

5.0 m

10 x 5 m (50 m

2

)

15 x 5 m (75 m

2

)

5.5 m

10 x 5 m (50 m

2

)

15 x 5 m (75 m

2

)

6.0 m

10 x 5 m (50 m

2

)

15 x 5 m (75 m

2

)

All fi gures are guidance values.

Brightness measurement

The presence detector measures artifi cial light and daylight 

by means of two directed light measurements. Light measu-

rement Z1 measures the brightness in zone 1. In zone 2, light 

measurement Z2 measures the brightness. The alignment of 

both brightness measurements has to be taken into account 

during installation. The installation location is the reference 

point for the lighting level. The brightness measurement can 

be adapted to the conditions in a room with the room correc-

tion factor. 

2 m

2 m

Z1

Z2

Each light measurement zone maps a rectangle of about 2 x 

4 m on the fl oor. Depending on the operating mode and the 

selected detection zone, the light measurements are assigned 

as follows:

1-channel (broadcast):

Selection of detection zone Lighting channel

Light measuring zone

Only zone 1

Channel C1 - light

Zone 1

Only zone 2

Channel C1 - light

Zone 2

Zone 1 + zone 2

Channel C1 - light

Ø from zone 1 + zone 2

2-channel (addressable):

Lighting channel

Light measuring zone

Channel C1 - light

Zone 1

Channel C2 - light

Zone 2

 

L

The alignment of both zone 1/zone 2 brightness measu-
rements must be taken into account!

 

L

Direct light infl uences the light measurement. Avoid pla-
cing fl oor lamps or suspended lighting directly under the 

detector.

Constant light control

The detector must be positioned in such a way that it only 

detects artifi cial light that it controls itself. Artifi cial light 

controlled by other detectors (or manually switched working 

lights) will affect the brightness measurement of the detector.

Switching mode

If the brightness measurement is deactivated, the lighting 

only switches based on the presence detection function 

(brightness setpoint value is set to «Measurement off» via the 

remote control).

Flush-mounted installation

with standard fl ush-mounting box, size 1

Surface-mounted installation

with LMS MG SURFACE MNT FRAME (B29011002)

Summary of Contents for B29004003

Page 1: ...the power supply and ensure that the parts are no longer live Read the entire manual and follow the instructions Prior to commissioning and using the product read the operating instructions 3 Proper use The presence detector is used in passageways stairca ses garages basements and warehouses for controlling the lighting and HVAC The presence detector is intended for indoor installation 4 Installat...

Page 2: ...nt zone maps a rectangle of about 2 x 4 m on the floor Depending on the operating mode and the selected detection zone the light measurements are assigned as follows 1 channel broadcast Selection of detection zone Lighting channel Light measuring zone Only zone 1 Channel C1 light Zone 1 Only zone 2 Channel C1 light Zone 2 Zone 1 zone 2 Channel C1 light Ø from zone 1 zone 2 2 channel addressable Li...

Page 3: ...r the addressable operating mode 6 Start up Initial operation of LMS MG PIR CLS SENSOR R LONG BC broadcast factory setting L LAfter the start up phase 30 s the detector is ready for operation Initial operation LMS MG PIR CLS SENSOR R LONG addressable unconfigured system The operating mode can be switched from broadcast to addressable with the LMS MG PROGRAM REMOTE BT App Select the LMS MG PIR CLS ...

Page 4: ... RC parameter to Enabled All connected buttons can be used for the configuration Press any button 5 times briefly 0 4 s and press and hold once 15 s The LED is switched off A DALI light starts to pulse random order The lighting group is assigned by pressing the approp riate button y y 1 x short button press channel C1 y y 2 x short button press channel C2 As confirmation the light dims to 20 3 s a...

Page 5: ...imming value 1 25 of the lamp output The standby time can be set between 0 s and 60 min or permanently If the room brightness is above the brightness setpoint value the lighting switches off If the room brightness is below the brightness setpoint value the lighting swit ches to the standby brightness If someone reenters the room the detector switches back automatically fully automatic device or af...

Page 6: ...ue Value range in x Parameter Description Can be checked via app Can be changed via app IR group address C1 Selection all I II III app to VIII x Scene 1 C1 Value range in x Scene 2 C1 Value range in x Configuration button RC Selection Enabled Disabled x LED motion display OFF ON x Checking the set values With the app and the app remote control parameters can be checked by gradually sending the val...

Page 7: ...e lux value Press Enter in the app A new window opens Enter the lux value and press OK The brightness measurement value appears in the display Important Press the send button After this the brightness measurement is calibrated The calculated room correction factor is adopted The room correction factor can be checked via the Room correction factor C1 parameter for monitoring purposes The default va...

Page 8: ...nge over to the LMS MG PIR CLS SENSOR R LONG detector type which owns 2 addressable lighting groups L LAfter changing over to the addressable mode the detector is in the emergency mode For programming the lighting groups see chapter 6 Start up Teach in C1 During the teach in process the currently measured bright ness value is adopted as brightness setpoint value C1 Values outside the permitted ran...

Page 9: ... x Response after man dimming Selection school office x Standby time Value range in seconds minutes Permanently on x Standby dimming value Value range in x Parameter Description Can be checked by app Can be changed by app IR group address C1 C2 Selection all I II III app to VIII x Scene 1 C1 scene 2 C1 Scene for lighting channel C1 value range in x Scene 1 C2 scene 2 C2 Scene for lighting channel ...

Page 10: ...er Automatic calibration Set up the LMS MG PROGRAM REMOTE BT according to the drawing and move a few steps away from the mea surement location so the lux measurement will not be influenced Press OK A new window with the measured brightness measu rement value is shown If you would like to apply this value Press OK Important Press the send button After this the brightness measurement is calibrated M...

Page 11: ... commands can be triggered with the remote control Control command Description Can be triggered by app DALI configuration Configuration of the lighting group operating mode DALI components Group assignment unaddress Configuration of the unaddressed lighting groups x Group assignment all Configuration of all lighting groups x Change group assignment Change configuration of the lighting groups x End...

Page 12: ...l settings of Broadcast LMS MG PIR CLS SENSOR R LONG BC Addressable LMS MG PIR CLS SENSOR R LONG Detection sensitivity The detector has 5 sensitivity increments The basic setting is the middle increment 3 Increments 1 to 5 can be selected and sent to the detector with the app in combination with the app remote control Value range Increment Sensitivity 1 Very insensitive 2 Insensitive 3 Standard 4 ...

Page 13: ...off the lighting after the set time 5 min 9 h The lighting is never switched off Never off Staircase light function Value range Glamox Sensor app The lighting can be switched on and off manually OFF The lighting can be switched on but not switched off manually It only switches off after the set time delay ON Dimming speed for manual dimming Value range Glamox Sensor app Dimming speed when dimming ...

Page 14: ...adially 30 x 5 m IH 3 5 m 150 m2 moving tangentially Setting range of brightness setpoint value 10 3000 lux Lighting time delay 10 s 60 min Presence switch on delay 0 s 10 min Presence time delay 10 s 120 min Lighting standby time 0 s 60 min permanently on Standby dimming value 1 25 Lighting control output DALI interface 100 mA max 50 DALI devices base insulation Connection type Screw terminals Ma...

Page 15: ... to clean the device surface Do not use any cleaning agents and solvents Disposal Dispose of device in environmentally sound manner 10 Dimensions diagrams 86 46 25 40 11 Contact Glamox AS BU Norway Hoffsveien 1C 0275 Oslo Postboks 163 Skøyen 0212 Oslo ...

Reviews: