14
LED display motion
Motion detection can be displayed using the LED.
Value range (Glamox Sensor-app)
No display of motion detection.
OFF
The LED is switched on when motion is detected, otherwise it
remains off.
ON
Presence test
The presence test mode checks the presence detection and
wiring. The presence test mode can be activated with the app
in combination with the app remote control. When the test
mode is set, the detector switches directly to test mode:
•
Every movement is indicated by the LED.
•
The lighting is switched on where there is movement.
•
If there is no movement, the lighting is switched off after
10 s.
•
The brightness measurement is deactivated, the detector
does not respond to brightness.
•
Constant light control is deactivated (switching mode).
•
The standby function is deactivated.
•
The detector responds as in the "fully automatic device"
configuration type – even if "semi-automatic device" is
set.
•
Teach-in cannot be activated in test mode.
•
The test mode ends after 10 min. The detector restarts
(see "Switch-on response").
Light test
The light test mode checks the brightness threshold and
the constant light control. The light test mode can be activa-
ted with the app in combination with the app remote control.
When the test mode is set, the detector switches directly to
test mode:
•
The LED shows the light test mode (5 seconds ON, 0.3
seconds OFF).
•
The presence detector responds as in the normal
operating mode; it only responds faster to brightness/
darkness.
•
To simulate the response, either actuate the blinds or
illuminate the area under the presence detector.
•
The test mode ends after 10 min. The detector restarts
(see "Switch-on response").
L
Note: Do not use a torch to trigger the presence detector
to switch! The adaptive light switching thresholds are
falsified!
Resetting the DALI EBs/DALI relays
The connected DALI EBs/DALI relays are reset to the factory
settings.
9. Technical data
Operating voltage
110–230 V AC, +10 %/–15 %
Frequency
50–60 Hz
Upstream protection device:
16 A
Power consumption (without DALI EB)
< 0.4 W
Type of installation
Ceiling installation; flush/
surface mounted or ceiling
installation
Recommended installation height
2.0–6.0 m
Minimum height
> 1.7 m
Detection area
horizontal 360°
Maximum range
20 x 5 m (IH 3.5 m)/100 m
2
moving radially
30 x 5 m (IH 3.5 m)/150 m
2
moving tangentially
Setting range of brightness setpoint
value
10–3000 lux
Lighting time delay
10 s–60 min
Presence switch-on delay
0 s–10 min
Presence time delay
10 s–120 min
Lighting standby time
0 s–60 min/permanently on
Standby dimming value
1–25 %
Lighting control output
DALI interface 100 mA, max. 50
DALI devices, base insulation
Connection type
Screw terminals
Max. cable cross-section
max. 2 x 2.5 mm²
Flush-mounted box size
Size 1, Ø 55 mm (NIS, PMI)
Protection rating
IP 54 when installed
Ambient temperature
–15 °C … 50 °C
CE Declaration of Conformity
This device conforms to the
safety regulations of the EMC
Directive 2014/30/EU and of
Directive 2014/35/EU.
Troubleshooting
Fault
Cause
Light does not switch
on or off if presence
is detected and in
darkness
Brightness setpoint value is set too low; detector
is set to semi-automatic device; light was switched
off manually using buttons or the LMS MG PRO-
GRAM REMOTE BT/LMS MG USER REMOTE; person
is not in the detection area; obstacle(s) disrupt
detection; time delay is too short
Light stays on with
detection of presence
despite sufficient
brightness
Brightness setpoint value is set too high; the light
was switched on manually a short while ago using
buttons or the LMS MG PROGRAM REMOTE BT/
LMS MG USER REMOTE (wait 30 min during swit-
ching mode); detector is in test mode
Light does not switch
off, or light switches on
spontaneously when
no one is present
Wait for time delay (self-learning);
thermal sources of interference in detection area;
fan heaters, light bulb/halogen spotlight, moving
objects (e.g. curtains in front of open windows)
Button does not work
Device still in the start-up phase; illuminated
button was used without neutral conductor;
button not connected to master.
Light cannot be
switched off with the
button
Button is not connected to the detector. Check the
button wiring.
Lighting does not
respond
Short circuit or interruption on DALI bus. Overvol-
tage on DALI bus: disconnect the detector from the
mains for 1 minute (thermal fuse).
Error flashing
(4 x per second)
Error in self-test;
device not functional!
LED is switched on and
flashes 2 x OFF briefly
every 3 s
The detector has not detected any DALI EBs. Check
DALI connections. At least 1 DALI EB must be con-
nected to the detector. Short circuit on DALI bus.
Master/slave, master/
master parallel swit-
ching is not working
The detector and button are not connected to the
same external conductor.