LED display motion

Motion detection can be displayed using the LED.

Value range (Glamox Sensor-app)

No display of motion detection.

OFF

The LED is switched on when motion is detected, otherwise it 

remains off.

ON

Presence test

The presence test mode checks the presence detection and 

wiring. The presence test mode can be activated with the app 

in combination with the app remote control. When the test 

mode is set, the detector switches directly to test mode:

 

Every movement is indicated by the LED.

 

The lighting is switched on where there is movement.

 

If there is no movement, the lighting is switched off after 
10 s.

 

The brightness measurement is deactivated, the detector 
does not respond to brightness.

 

Constant light control is deactivated (switching mode).

 

The standby function is deactivated.

 

The detector responds as in the "fully automatic device" 

configuration type – even if "semi-automatic device" is 

set.

 

Teach-in cannot be activated in test mode.

 

The test mode ends after 10 min. The detector restarts 
(see "Switch-on response").

Light test

The light test mode checks the brightness threshold and  

the constant light control. The light test mode can be activa-

ted with the app in combination with the app remote control. 

When the test mode is set, the detector switches directly to 

test mode:

 

The LED shows the light test mode (5 seconds ON, 0.3 
seconds OFF).

 

The presence detector responds as in the normal 
operating mode; it only responds faster to brightness/
darkness.

 

To simulate the response, either actuate the blinds or 
illuminate the area under the presence detector.

 

The test mode ends after 10 min. The detector restarts 
(see "Switch-on response").

 

L

Note: Do not use a torch to trigger the presence detector 
to switch! The adaptive light switching thresholds are 

falsified!

Resetting the DALI EBs/DALI relays

The connected DALI EBs/DALI relays are reset to the factory 

settings.

9.  Technical data

Operating voltage

110–230 V AC, +10 %/–15 %

Frequency

50–60 Hz

Upstream protection device:

16 A

Power consumption (without DALI EB)

< 0.4 W

Type of installation

Ceiling installation; flush/

surface mounted or ceiling 

installation

Recommended installation height

2.0–6.0 m

Minimum height

> 1.7 m

Detection area 

horizontal 360°

Maximum range

20 x 5 m (IH 3.5 m)/100 m

2

 

moving radially

30 x 5 m (IH 3.5 m)/150 m

2

 

moving tangentially

Setting range of brightness setpoint 

value

10–3000 lux

Lighting time delay

10 s–60 min

Presence switch-on delay

0 s–10 min

Presence time delay

10 s–120 min

Lighting standby time

0 s–60 min/permanently on

Standby dimming value

1–25 %

Lighting control output

DALI interface 100 mA, max. 50 

DALI devices, base insulation

Connection type

Screw terminals

Max. cable cross-section

max. 2 x 2.5 mm²

Flush-mounted box size

Size 1, Ø 55 mm (NIS, PMI)

Protection rating

IP 54 when installed

Ambient temperature

–15 °C … 50 °C

CE Declaration of Conformity

This device conforms to the 

safety regulations of the EMC 

Directive 2014/30/EU and of 

Directive 2014/35/EU. 

Troubleshooting

Fault

Cause

Light does not switch 

on or off if presence 

is detected and in 

darkness

Brightness setpoint value is set too low; detector 

is set to semi-automatic device; light was switched 

off manually using buttons or the LMS MG PRO-

GRAM REMOTE BT/LMS MG USER REMOTE; person 

is not in the detection area; obstacle(s) disrupt 

detection; time delay is too short

Light stays on with 

detection of presence 

despite sufficient 

brightness 

Brightness setpoint value is set too high; the light 

was switched on manually a short while ago using 

buttons or the LMS MG PROGRAM REMOTE BT/

LMS MG USER REMOTE (wait 30 min during swit-

ching mode); detector is in test mode

Light does not switch 

off, or light switches on 

spontaneously when 

no one is present 

Wait for time delay (self-learning); 

thermal sources of interference in detection area; 

fan heaters, light bulb/halogen spotlight, moving 

objects (e.g. curtains in front of open windows)

Button does not work

Device still in the start-up phase; illuminated 

button was used without neutral conductor;  

button not connected to master. 

Light cannot be 

switched off with the 

button

Button is not connected to the detector. Check the 

button wiring.

Lighting does not 

respond

Short circuit or interruption on DALI bus. Overvol-

tage on DALI bus: disconnect the detector from the 

mains for 1 minute (thermal fuse).

Error flashing 

 

(4 x per second)

Error in self-test; 

device not functional!

LED is switched on and 

flashes 2 x OFF briefly 

every 3 s

The detector has not detected any DALI EBs. Check 

DALI connections. At least 1 DALI EB must be con-

nected to the detector. Short circuit on DALI bus.

Master/slave, master/

master parallel swit-

ching is not working

The detector and button are not connected to the 

same external conductor. 

Summary of Contents for B29004003

Page 1: ...the power supply and ensure that the parts are no longer live Read the entire manual and follow the instructions Prior to commissioning and using the product read the operating instructions 3 Proper use The presence detector is used in passageways stairca ses garages basements and warehouses for controlling the lighting and HVAC The presence detector is intended for indoor installation 4 Installat...

Page 2: ...nt zone maps a rectangle of about 2 x 4 m on the floor Depending on the operating mode and the selected detection zone the light measurements are assigned as follows 1 channel broadcast Selection of detection zone Lighting channel Light measuring zone Only zone 1 Channel C1 light Zone 1 Only zone 2 Channel C1 light Zone 2 Zone 1 zone 2 Channel C1 light Ø from zone 1 zone 2 2 channel addressable Li...

Page 3: ...r the addressable operating mode 6 Start up Initial operation of LMS MG PIR CLS SENSOR R LONG BC broadcast factory setting L LAfter the start up phase 30 s the detector is ready for operation Initial operation LMS MG PIR CLS SENSOR R LONG addressable unconfigured system The operating mode can be switched from broadcast to addressable with the LMS MG PROGRAM REMOTE BT App Select the LMS MG PIR CLS ...

Page 4: ... RC parameter to Enabled All connected buttons can be used for the configuration Press any button 5 times briefly 0 4 s and press and hold once 15 s The LED is switched off A DALI light starts to pulse random order The lighting group is assigned by pressing the approp riate button y y 1 x short button press channel C1 y y 2 x short button press channel C2 As confirmation the light dims to 20 3 s a...

Page 5: ...imming value 1 25 of the lamp output The standby time can be set between 0 s and 60 min or permanently If the room brightness is above the brightness setpoint value the lighting switches off If the room brightness is below the brightness setpoint value the lighting swit ches to the standby brightness If someone reenters the room the detector switches back automatically fully automatic device or af...

Page 6: ...ue Value range in x Parameter Description Can be checked via app Can be changed via app IR group address C1 Selection all I II III app to VIII x Scene 1 C1 Value range in x Scene 2 C1 Value range in x Configuration button RC Selection Enabled Disabled x LED motion display OFF ON x Checking the set values With the app and the app remote control parameters can be checked by gradually sending the val...

Page 7: ...e lux value Press Enter in the app A new window opens Enter the lux value and press OK The brightness measurement value appears in the display Important Press the send button After this the brightness measurement is calibrated The calculated room correction factor is adopted The room correction factor can be checked via the Room correction factor C1 parameter for monitoring purposes The default va...

Page 8: ...nge over to the LMS MG PIR CLS SENSOR R LONG detector type which owns 2 addressable lighting groups L LAfter changing over to the addressable mode the detector is in the emergency mode For programming the lighting groups see chapter 6 Start up Teach in C1 During the teach in process the currently measured bright ness value is adopted as brightness setpoint value C1 Values outside the permitted ran...

Page 9: ... x Response after man dimming Selection school office x Standby time Value range in seconds minutes Permanently on x Standby dimming value Value range in x Parameter Description Can be checked by app Can be changed by app IR group address C1 C2 Selection all I II III app to VIII x Scene 1 C1 scene 2 C1 Scene for lighting channel C1 value range in x Scene 1 C2 scene 2 C2 Scene for lighting channel ...

Page 10: ...er Automatic calibration Set up the LMS MG PROGRAM REMOTE BT according to the drawing and move a few steps away from the mea surement location so the lux measurement will not be influenced Press OK A new window with the measured brightness measu rement value is shown If you would like to apply this value Press OK Important Press the send button After this the brightness measurement is calibrated M...

Page 11: ... commands can be triggered with the remote control Control command Description Can be triggered by app DALI configuration Configuration of the lighting group operating mode DALI components Group assignment unaddress Configuration of the unaddressed lighting groups x Group assignment all Configuration of all lighting groups x Change group assignment Change configuration of the lighting groups x End...

Page 12: ...l settings of Broadcast LMS MG PIR CLS SENSOR R LONG BC Addressable LMS MG PIR CLS SENSOR R LONG Detection sensitivity The detector has 5 sensitivity increments The basic setting is the middle increment 3 Increments 1 to 5 can be selected and sent to the detector with the app in combination with the app remote control Value range Increment Sensitivity 1 Very insensitive 2 Insensitive 3 Standard 4 ...

Page 13: ...off the lighting after the set time 5 min 9 h The lighting is never switched off Never off Staircase light function Value range Glamox Sensor app The lighting can be switched on and off manually OFF The lighting can be switched on but not switched off manually It only switches off after the set time delay ON Dimming speed for manual dimming Value range Glamox Sensor app Dimming speed when dimming ...

Page 14: ...adially 30 x 5 m IH 3 5 m 150 m2 moving tangentially Setting range of brightness setpoint value 10 3000 lux Lighting time delay 10 s 60 min Presence switch on delay 0 s 10 min Presence time delay 10 s 120 min Lighting standby time 0 s 60 min permanently on Standby dimming value 1 25 Lighting control output DALI interface 100 mA max 50 DALI devices base insulation Connection type Screw terminals Ma...

Page 15: ... to clean the device surface Do not use any cleaning agents and solvents Disposal Dispose of device in environmentally sound manner 10 Dimensions diagrams 86 46 25 40 11 Contact Glamox AS BU Norway Hoffsveien 1C 0275 Oslo Postboks 163 Skøyen 0212 Oslo ...

Reviews: