4
•
All connected buttons are active. Switching on and off as
well as dimming are possible.
•
Time delay: 10 min.
Configuring the lighting groups with
•
LMS MG PROGRAM REMOTE BT/Glamox Sensor-app
•
Buttons or LMS MG USER REMOTE
Configuring the lighting groups with the LMS MG PROGRAM
REMOTE BT/App
Connect the LMS MG PROGRAM REMOTE BT with the corre-
sponding Glamox Sensor-app.
Place the LMS MG PROGRAM REMOTE BT under the detec-
tor (direct the remote control towards the detector).
Select LMS MG PIR CLS SENSOR-R LONG as the type in the
app.
In the "DALI configuration" menu, select the required group
assignment.
For the DALI configuration, there are 3 options available:
y
"Group assignment (unaddress.)": only DALI EBs without a
group address are processed.
y
"Group assignment (all)": all connected DALI EBs are con-
figured.
NOTE
: All existing group assignments with group
number 1 or 2 are deleted.
y
"Change group assignment": the next existing EB is
searched for and selected.
▻
After selecting the required group assignment, the
detector is in the programming mode.
▻
A DALI light starts to pulse (random order).
Use to assign the required C1 or C2 channel to the DALI
EB.
▻ As confirmation, the light dims to 20%.
▻
The next DALI light starts to pulse. One after the other,
the lighting groups are assigned to all the lights.
•
For group assignment (unaddress.) or (all): if all DALI EBs
are assigned to a lighting group, the detector terminates
the configuration process and restarts (startup phase of
30 s). The detector then switches to the normal opera-
ting mode and the configuration is completed.
L
If necessary, the configuration process can be ended by
pressing „End“ (left function button).
▻
In this case, the system is not ready for operation.
•
If „Change group assignment“ has been selected, use the
right „>“ button to switch to the next DALI EB without
changing the lighting group.
When all required changes have been made, end the confi
-
guration process by pressing „End“ (left function button).
Configuring the lighting groups using buttons
Set the <Configuration button/RC> parameter to "Enabled".
All connected buttons can be used for the configuration.
Press any button 5 times briefly (< 0.4 s) and press and
hold once (> 15 s).
▻
The LED is switched off.
▻
A DALI light starts to pulse (random order).
▻
The lighting group is assigned by pressing the approp-
riate button:
y
1 x short button press = channel C1
y
2 x short button press = channel C2
▻ As confirmation, the light dims to 20 % (3 s after the
last button press).
▻
The next DALI light starts to pulse. One after the other,
the lighting groups are assigned to all the lights.
•
If all DALI EBs are assigned to a lighting group, the
detector terminates the configuration process and
restarts (startup phase of 30 s).
▻
The detector switches to the normal operating mode
and the configuration is completed.
L
If required, the configuration process can be ended by
pressing and holding any button for longer than 15 s.
The detector restarts.
▻
In this case, the system is not ready for operation.
L
Instead of using the button, the configuration can also
be carried out with the ON/OFF buttons on the LMS MG
PROGRAM REMOTE BT/LMS MG USER REMOTE.
Checking the configuration
The assignment of the lighting groups can be checked by
switching the individual lighting groups on or off using but-
tons, the LMS MG PROGRAM REMOTE BT/App (for the app,
select the "Control commands" menu).
L
Changing the lighting group for DALI EBs: use the LMS MG
PROGRAM REMOTE BT/App to change the DALI configura
-
tion via the "Change group assignment" command.
L
With the button: the whole DALI configuration must be
re-executed.
Switch-on response (configured system)
If voltage is applied, the presence detector goes through two
phases which are indicated by the LED:
1. Start-up phase (30 s)
•
The red LED flashes in one-second intervals; the lighting
is switched on with the switch on dimming value.
•
The detector does not react to button commands or
to the LMS MG PROGRAM REMOTE BT/LMS MG USER
REMOTE.
•
If absent, the lighting is switched off after 30 s.
2. Operation
•
The red LED is off. The constant light control or switching
mode are started.
▻
The detector is ready for operation.
7. Functions
Z1
Z2
Mixed light measurement
Presence detection
Artificial light
Button for manual lighting control