background image

4

 

All connected buttons are active. Switching on and off as 
well as dimming are possible.

 

Time delay: 10 min.

Configuring the lighting groups with

 

LMS MG PROGRAM REMOTE BT/Glamox Sensor-app

 

Buttons or LMS MG USER REMOTE

Configuring the lighting groups with the LMS MG PROGRAM 

REMOTE BT/App

†

†

Connect the LMS MG PROGRAM REMOTE BT with the corre-

sponding Glamox Sensor-app.

†

†

Place the LMS MG PROGRAM REMOTE BT under the detec-

tor (direct the remote control towards the detector).

†

†

Select LMS MG PIR CLS SENSOR-R LONG as the type in the 

app.

†

†

In the "DALI configuration" menu, select the required group 

assignment.

For the DALI configuration, there are 3 options available:

†

y

"Group assignment (unaddress.)": only DALI EBs without a 

group address are processed.

†

y

"Group assignment (all)": all connected DALI EBs are con-

figured. 

NOTE

: All existing group assignments with group 

number 1 or 2 are deleted.

†

y

"Change group assignment": the next existing EB is 

searched for and selected.

 

After selecting the required group assignment, the 
detector is in the programming mode.

 

A DALI light starts to pulse (random order).

†

†

Use   to assign the required C1 or C2 channel to the DALI 

EB. 

 

▻ As confirmation, the light dims to 20%. 

 

The next DALI light starts to pulse. One after the other, 
the lighting groups are assigned to all the lights. 

 

For group assignment (unaddress.) or (all): if all DALI EBs 
are assigned to a lighting group, the detector terminates 

the configuration process and restarts (startup phase of 

30 s). The detector then switches to the normal opera-

ting mode and the configuration is completed.

 

L

If necessary, the configuration process can be ended by 

pressing „End“ (left function button). 

 

In this case, the system is not ready for operation.

 

If „Change group assignment“ has been selected, use the 
right „>“ button to switch to the next DALI EB without 
changing the lighting group.

†

†

When all required changes have been made, end the confi

-

guration process by pressing „End“ (left function button).

Configuring the lighting groups using buttons

†

†

Set the <Configuration button/RC> parameter to "Enabled". 

All connected buttons can be used for the configuration.

†

†

Press any button 5 times briefly (< 0.4 s) and press and 

hold once (> 15 s).

 

The LED is switched off.

 

A DALI light starts to pulse (random order).

 

The lighting group is assigned by pressing the approp-
riate button:

†

y

1 x short button press = channel C1

†

y

2 x short button press = channel C2 

 

▻ As confirmation, the light dims to 20 % (3 s after the 

last button press). 

 

The next DALI light starts to pulse. One after the other, 
the lighting groups are assigned to all the lights. 

 

If all DALI EBs are assigned to a lighting group, the 

detector terminates the configuration process and 

restarts (startup phase of 30 s). 

 

The detector switches to the normal operating mode 

and the configuration is completed.

 

L

If required, the configuration process can be ended by 

pressing and holding any button for longer than 15 s.  
The detector restarts. 

 

In this case, the system is not ready for operation.

 

L

Instead of using the button, the configuration can also 

be carried out with the ON/OFF buttons on the LMS MG 
PROGRAM REMOTE BT/LMS MG USER REMOTE.

Checking the configuration

The assignment of the lighting groups can be checked by 

switching the individual lighting groups on or off using but-

tons, the LMS MG PROGRAM REMOTE BT/App (for the app, 

select the "Control commands" menu).

 

L

Changing the lighting group for DALI EBs: use the LMS MG 

PROGRAM REMOTE BT/App to change the DALI configura

-

tion via the "Change group assignment" command. 

 

L

With the button: the whole DALI configuration must be 

re-executed.

Switch-on response (configured system)

If voltage is applied, the presence detector goes through two 

phases which are indicated by the LED:

1. Start-up phase (30 s)

 

The red LED flashes in one-second intervals; the lighting 

is switched on with the switch on dimming value.

 

The detector does not react to button commands or 
to the LMS MG PROGRAM REMOTE BT/LMS MG USER 
REMOTE.

 

If absent, the lighting is switched off after 30 s.

2. Operation

 

The red LED is off. The constant light control or switching 
mode are started.

 

The detector is ready for operation.

7.  Functions

Z1

Z2

 Mixed light measurement 

 Presence detection

 Artificial light

 Button for manual lighting control

 Incident daylight

Summary of Contents for B29004003

Page 1: ...the power supply and ensure that the parts are no longer live Read the entire manual and follow the instructions Prior to commissioning and using the product read the operating instructions 3 Proper use The presence detector is used in passageways stairca ses garages basements and warehouses for controlling the lighting and HVAC The presence detector is intended for indoor installation 4 Installat...

Page 2: ...nt zone maps a rectangle of about 2 x 4 m on the floor Depending on the operating mode and the selected detection zone the light measurements are assigned as follows 1 channel broadcast Selection of detection zone Lighting channel Light measuring zone Only zone 1 Channel C1 light Zone 1 Only zone 2 Channel C1 light Zone 2 Zone 1 zone 2 Channel C1 light Ø from zone 1 zone 2 2 channel addressable Li...

Page 3: ...r the addressable operating mode 6 Start up Initial operation of LMS MG PIR CLS SENSOR R LONG BC broadcast factory setting L LAfter the start up phase 30 s the detector is ready for operation Initial operation LMS MG PIR CLS SENSOR R LONG addressable unconfigured system The operating mode can be switched from broadcast to addressable with the LMS MG PROGRAM REMOTE BT App Select the LMS MG PIR CLS ...

Page 4: ... RC parameter to Enabled All connected buttons can be used for the configuration Press any button 5 times briefly 0 4 s and press and hold once 15 s The LED is switched off A DALI light starts to pulse random order The lighting group is assigned by pressing the approp riate button y y 1 x short button press channel C1 y y 2 x short button press channel C2 As confirmation the light dims to 20 3 s a...

Page 5: ...imming value 1 25 of the lamp output The standby time can be set between 0 s and 60 min or permanently If the room brightness is above the brightness setpoint value the lighting switches off If the room brightness is below the brightness setpoint value the lighting swit ches to the standby brightness If someone reenters the room the detector switches back automatically fully automatic device or af...

Page 6: ...ue Value range in x Parameter Description Can be checked via app Can be changed via app IR group address C1 Selection all I II III app to VIII x Scene 1 C1 Value range in x Scene 2 C1 Value range in x Configuration button RC Selection Enabled Disabled x LED motion display OFF ON x Checking the set values With the app and the app remote control parameters can be checked by gradually sending the val...

Page 7: ...e lux value Press Enter in the app A new window opens Enter the lux value and press OK The brightness measurement value appears in the display Important Press the send button After this the brightness measurement is calibrated The calculated room correction factor is adopted The room correction factor can be checked via the Room correction factor C1 parameter for monitoring purposes The default va...

Page 8: ...nge over to the LMS MG PIR CLS SENSOR R LONG detector type which owns 2 addressable lighting groups L LAfter changing over to the addressable mode the detector is in the emergency mode For programming the lighting groups see chapter 6 Start up Teach in C1 During the teach in process the currently measured bright ness value is adopted as brightness setpoint value C1 Values outside the permitted ran...

Page 9: ... x Response after man dimming Selection school office x Standby time Value range in seconds minutes Permanently on x Standby dimming value Value range in x Parameter Description Can be checked by app Can be changed by app IR group address C1 C2 Selection all I II III app to VIII x Scene 1 C1 scene 2 C1 Scene for lighting channel C1 value range in x Scene 1 C2 scene 2 C2 Scene for lighting channel ...

Page 10: ...er Automatic calibration Set up the LMS MG PROGRAM REMOTE BT according to the drawing and move a few steps away from the mea surement location so the lux measurement will not be influenced Press OK A new window with the measured brightness measu rement value is shown If you would like to apply this value Press OK Important Press the send button After this the brightness measurement is calibrated M...

Page 11: ... commands can be triggered with the remote control Control command Description Can be triggered by app DALI configuration Configuration of the lighting group operating mode DALI components Group assignment unaddress Configuration of the unaddressed lighting groups x Group assignment all Configuration of all lighting groups x Change group assignment Change configuration of the lighting groups x End...

Page 12: ...l settings of Broadcast LMS MG PIR CLS SENSOR R LONG BC Addressable LMS MG PIR CLS SENSOR R LONG Detection sensitivity The detector has 5 sensitivity increments The basic setting is the middle increment 3 Increments 1 to 5 can be selected and sent to the detector with the app in combination with the app remote control Value range Increment Sensitivity 1 Very insensitive 2 Insensitive 3 Standard 4 ...

Page 13: ...off the lighting after the set time 5 min 9 h The lighting is never switched off Never off Staircase light function Value range Glamox Sensor app The lighting can be switched on and off manually OFF The lighting can be switched on but not switched off manually It only switches off after the set time delay ON Dimming speed for manual dimming Value range Glamox Sensor app Dimming speed when dimming ...

Page 14: ...adially 30 x 5 m IH 3 5 m 150 m2 moving tangentially Setting range of brightness setpoint value 10 3000 lux Lighting time delay 10 s 60 min Presence switch on delay 0 s 10 min Presence time delay 10 s 120 min Lighting standby time 0 s 60 min permanently on Standby dimming value 1 25 Lighting control output DALI interface 100 mA max 50 DALI devices base insulation Connection type Screw terminals Ma...

Page 15: ... to clean the device surface Do not use any cleaning agents and solvents Disposal Dispose of device in environmentally sound manner 10 Dimensions diagrams 86 46 25 40 11 Contact Glamox AS BU Norway Hoffsveien 1C 0275 Oslo Postboks 163 Skøyen 0212 Oslo ...

Reviews: