8
With the LMS MG USER REMOTE or the LMS MG PROGRAM
REMOTE BT, the lighting is set to a required brightness and
saved as follows:
Press the button for at least 3 s.
Scene 1 has been
saved
Press the button for at least 3 s.
Scene 2 has been
saved
The scene can be opened by briefly pressing the button.
Control commands via remote control
The following control commands can be triggered with the
remote control:
Control
command
Description
Can be triggered
by the app
DALI
configuration
Configuration of the operating
mode/DALI components
Change over to
"addressable"
operating mode
Changeover from "broadcast" to
"addressable". After the changeover,
<LMS MG PIR CLS SENSOR-R LONG>
must be selected as the type.
x
Reset DALI EBs
All connected DALI EBs are reset to
the factory setting.
x
Reset DALI relay The connected DALI relay is reset to
the factory setting.
x
Switching light
The lighting group can be switched
on and off.
x
Teach-in C1
Activation
x
Presence test
OFF/ON
x
Light test
OFF/ON
x
Restart
Restart the detector
x
Factory settings Set all parameters and settings to
the factory setting.
x
Changing over to "addressable" operating mode
In factory setting, the detector is in the broadcast operating
mode (type <LMS MG PIR CLS SENSOR-R LONG BC>). Use the
control command to change over to the <LMS MG PIR CLS
SENSOR-R LONG> detector type which owns 2 addressable
lighting groups.
L
After changing over to the addressable mode, the detector
is in the emergency mode. For programming the lighting
groups, see chapter 6 "Start-up".
Teach-in C1
During the teach-in process, the currently measured bright-
ness value is adopted as brightness setpoint value C1. Values
outside the permitted range are automatically set to the
appropriate limit value.
The teach-in control command can be executed with the app
or the app remote control.
Factory settings
The presence detector is supplied with the following parame-
ter values: LMS MG PIR CLS SENSOR-R LONG BC
Parameter
Value
Detection zone
Z1+Z2
Function C1
Control
Brightness setpoint value C1
200 lux
Room correction factor C1
0.3
Detection sensitivity (PIR)
Increment 3
Lighting time delay
5 min
Short-term presence
ON
Energy saving mode
eco
Presence switch-on delay
0 s
Presence time delay
10 min
Switch on dimming value C1
50 %
Configuration type
auto
Control speed
Standard
Minimum dimming value
10 %
Maximum dimming value
100 %
Switch off brightness
10 min
Staircase light function
OFF
Dimming speed: man. dimming
Standard
Response after man. dimming
School
Standby time
0 s
Standby dimming value
10 %
IR group address C1
I
Scene 1 C1
30 %
Scene 2 C1
70 %
Configuration button/RC
Enabled
LED motion display
OFF
L
The parameters can only be reset to the factory setting
with the app in combination the app remote control.