Broadcast <LMS MG PIR CLS SENSOR-R LONG BC>

Teach-in via button

†

†

Press the button for > 15 s 

 

The currently measured brightness value is adopted as 
the brightness setpoint value.

 

L

The teach-in function via the button can be disabled using 

the app remote control when the "Configuration button/

RC" parameter is set to "disabled".

Parameters via remote control

The following parameters can be checked or changed via 

the remote control for support during start-up as well as 

servicing:

Parameter

Description

Can be 

checked via 

app

Can be 

changed via 

app

Detection zone

Selection: Z1/Z2/Z1+Z2

x

x

Function C1

Selection: switching/

control

x

x

Brightness set-

point value C1

Value range in lux/measu-

rement off

x

x

Brightness actual 

value C1

Check brightness actual 

value

x

Room correction 

factor C1

Room correction factor

x

x

Brightness 

measurement 

value C1

Lux meter brightness value 

in lux

x

Detection sensi-

tivity (PIR)

Value range in increments

x

x

Lighting time 

delay

Value range in seconds/

minutes

x

Short-term 

presence

Short-term presence: ON/

OFF

x

x

Energy saving 

mode

Selection: eco/eco plus

x

x

Presence switch-

on delay

Value range in seconds/

minutes

x

Presence time 

delay

Value range in seconds/

minutes

x

Switch on dim-

ming value C1

Value range in %

x

Configuration 

type C1

Selection: Auto/Man

x

x

Control speed

Selection: standard/

average/fast

x

Minimum dim-

ming value

Value range in %

x

Maximum dim-

ming value

Value range in %

x

Switch off 

brightness

Value range in minutes/

hours/never off

x

Staircase light 

function

Selection: ON/OFF

x

x

Dimming speed: 

man. dimming

Selection: standard/fast

x

Response after 

man. dimming

Selection: school/office

x

Standby time

Value range in seconds/

minutes/Permanently on

x

Standby dimming 

value

Value range in %

x

Parameter

Description

Can be 

checked via 

app

Can be 

changed via 

app

IR group address 

C1

Selection: all/I/II/III (app 

to VIII)

x

Scene 1 C1

Value range in %

x

Scene 2 C1

Value range in %

x

Configuration 

button/RC

Selection: Enabled/

Disabled

x

LED motion 

display

OFF/ON

x

Checking the set values:

With the app and the app remote control, parameters can be 

checked by gradually sending the values to the detector. If 

the sent value is below the set parameter, the LED lights up 

briefly. If the sent value is equal to or above the set parameter, 

the LED lights flickers for 2 s.

Detection zone

The detection area is divided into two independent detec-

tion zones (see 4. Installation, detection area). For a maxi-

mum range, zone 1 and zone 2 are activated. If a limitation 

of the detection area is required, zone 1 or zone 2 can be 

deactivated.

Value range (Glamox Sensor-app)

Selection of detection area

Z1, Z2, Z1 and Z2

Function C1

The lighting channel C1 can be operated in switching mode or 

in the constant light control function. The function is set via 

the <Function C1> parameter. 

Value range (Glamox Sensor-app)

Switching

Lighting channel C1 is in the switching mode function

Control

Lighting channel C1 is in the constant light control function

Brightness setpoint value C1

The brightness setpoint value defines the minimum required 

brightness. The current brightness is measured below the 

presence detector. If the brightness is below the setpoint 

value and presence is detected, the light is switched on (for 

the fully automatic device configuration type).

Value range (app)

Brightness setpoint value min.

10–3000 lux

Deactivation of brightness measurement (brightness 

measurement has no effect)

The lighting channels only switch according to presence 

and absence.

Measurement off

Brightness actual value C1

The brightness actual value can be checked for monitoring 

purposes. To check, see the "Parameters via remote control" 

table.

Summary of Contents for B29004003

Page 1: ...the power supply and ensure that the parts are no longer live Read the entire manual and follow the instructions Prior to commissioning and using the product read the operating instructions 3 Proper use The presence detector is used in passageways stairca ses garages basements and warehouses for controlling the lighting and HVAC The presence detector is intended for indoor installation 4 Installat...

Page 2: ...nt zone maps a rectangle of about 2 x 4 m on the floor Depending on the operating mode and the selected detection zone the light measurements are assigned as follows 1 channel broadcast Selection of detection zone Lighting channel Light measuring zone Only zone 1 Channel C1 light Zone 1 Only zone 2 Channel C1 light Zone 2 Zone 1 zone 2 Channel C1 light Ø from zone 1 zone 2 2 channel addressable Li...

Page 3: ...r the addressable operating mode 6 Start up Initial operation of LMS MG PIR CLS SENSOR R LONG BC broadcast factory setting L LAfter the start up phase 30 s the detector is ready for operation Initial operation LMS MG PIR CLS SENSOR R LONG addressable unconfigured system The operating mode can be switched from broadcast to addressable with the LMS MG PROGRAM REMOTE BT App Select the LMS MG PIR CLS ...

Page 4: ... RC parameter to Enabled All connected buttons can be used for the configuration Press any button 5 times briefly 0 4 s and press and hold once 15 s The LED is switched off A DALI light starts to pulse random order The lighting group is assigned by pressing the approp riate button y y 1 x short button press channel C1 y y 2 x short button press channel C2 As confirmation the light dims to 20 3 s a...

Page 5: ...imming value 1 25 of the lamp output The standby time can be set between 0 s and 60 min or permanently If the room brightness is above the brightness setpoint value the lighting switches off If the room brightness is below the brightness setpoint value the lighting swit ches to the standby brightness If someone reenters the room the detector switches back automatically fully automatic device or af...

Page 6: ...ue Value range in x Parameter Description Can be checked via app Can be changed via app IR group address C1 Selection all I II III app to VIII x Scene 1 C1 Value range in x Scene 2 C1 Value range in x Configuration button RC Selection Enabled Disabled x LED motion display OFF ON x Checking the set values With the app and the app remote control parameters can be checked by gradually sending the val...

Page 7: ...e lux value Press Enter in the app A new window opens Enter the lux value and press OK The brightness measurement value appears in the display Important Press the send button After this the brightness measurement is calibrated The calculated room correction factor is adopted The room correction factor can be checked via the Room correction factor C1 parameter for monitoring purposes The default va...

Page 8: ...nge over to the LMS MG PIR CLS SENSOR R LONG detector type which owns 2 addressable lighting groups L LAfter changing over to the addressable mode the detector is in the emergency mode For programming the lighting groups see chapter 6 Start up Teach in C1 During the teach in process the currently measured bright ness value is adopted as brightness setpoint value C1 Values outside the permitted ran...

Page 9: ... x Response after man dimming Selection school office x Standby time Value range in seconds minutes Permanently on x Standby dimming value Value range in x Parameter Description Can be checked by app Can be changed by app IR group address C1 C2 Selection all I II III app to VIII x Scene 1 C1 scene 2 C1 Scene for lighting channel C1 value range in x Scene 1 C2 scene 2 C2 Scene for lighting channel ...

Page 10: ...er Automatic calibration Set up the LMS MG PROGRAM REMOTE BT according to the drawing and move a few steps away from the mea surement location so the lux measurement will not be influenced Press OK A new window with the measured brightness measu rement value is shown If you would like to apply this value Press OK Important Press the send button After this the brightness measurement is calibrated M...

Page 11: ... commands can be triggered with the remote control Control command Description Can be triggered by app DALI configuration Configuration of the lighting group operating mode DALI components Group assignment unaddress Configuration of the unaddressed lighting groups x Group assignment all Configuration of all lighting groups x Change group assignment Change configuration of the lighting groups x End...

Page 12: ...l settings of Broadcast LMS MG PIR CLS SENSOR R LONG BC Addressable LMS MG PIR CLS SENSOR R LONG Detection sensitivity The detector has 5 sensitivity increments The basic setting is the middle increment 3 Increments 1 to 5 can be selected and sent to the detector with the app in combination with the app remote control Value range Increment Sensitivity 1 Very insensitive 2 Insensitive 3 Standard 4 ...

Page 13: ...off the lighting after the set time 5 min 9 h The lighting is never switched off Never off Staircase light function Value range Glamox Sensor app The lighting can be switched on and off manually OFF The lighting can be switched on but not switched off manually It only switches off after the set time delay ON Dimming speed for manual dimming Value range Glamox Sensor app Dimming speed when dimming ...

Page 14: ...adially 30 x 5 m IH 3 5 m 150 m2 moving tangentially Setting range of brightness setpoint value 10 3000 lux Lighting time delay 10 s 60 min Presence switch on delay 0 s 10 min Presence time delay 10 s 120 min Lighting standby time 0 s 60 min permanently on Standby dimming value 1 25 Lighting control output DALI interface 100 mA max 50 DALI devices base insulation Connection type Screw terminals Ma...

Page 15: ... to clean the device surface Do not use any cleaning agents and solvents Disposal Dispose of device in environmentally sound manner 10 Dimensions diagrams 86 46 25 40 11 Contact Glamox AS BU Norway Hoffsveien 1C 0275 Oslo Postboks 163 Skøyen 0212 Oslo ...

Reviews: