Room correction factor C1, brightness measurement
value C1
The room correction factor is a measure of the different
brightness measurements at the ceiling and on the work
surface (the brightness value depends on the ambient
conditions).
2,5 m
2,5 m
Z1
Z2
theSenda B
oder Luxmeter
LMS MG PROGRAM REMOTE BT
or lux meter
Room correction factor = Brightness value at the ceiling
Brightness value on the floor
The brightness measurement value at the ceiling is influenced
by the installation location, incidence of light, position of the
sun, weather conditions, the reflection properties of the room,
and the furniture. In order to be able to adhere to the requi-
red lux value in the desired area, a comparison of the bright-
ness measurements is necessary.
The measured lux meter value
below the presence detector
is sent to the detector via the remote control.
When sending the brightness measurement value, the room
correction factor of the corresponding lighting channel is
automatically adjusted to the conditions inside the room.
Two different procedures can be selected in the app for the
comparison (automatic/manual calibration).
Connect the app remote control LMS MG PROGRAM
REMOTE BT with the corresponding Glamox Sensor-app.
Select the appropriate detector type <LMS MG PIR CLS
SENSOR-R LONG BC> and load the parameter set.
Select the <Brightness measurement value C1> parameter.
Automatic calibration
Set up the LMS MG PROGRAM REMOTE BT according to
the drawing, and move a few steps away from the mea-
surement location, so the lux measurement will not be
influenced.
Press OK.
▻
A new window with the measured brightness measu-
rement value is shown. If you would like to apply this
value,
Press OK.
Important
: Press the send button ( ). After this, the
brightness measurement is calibrated.
Manuel calibration using the lux meter
Set up or align the lux meter according to the drawing, and
read the lux value.
Press "Enter" in the app.
▻
A new window opens.
Enter the lux value and press OK.
▻
The brightness measurement value appears in the
display.
Important
: Press the send button ( ). After this, the
brightness measurement is calibrated.
•
The calculated room correction factor is adopted. The
room correction factor can be checked via the <Room
correction factor C1> parameter for monitoring purposes.
The default value is 0.3.
Switch on dimming value C1
In switching mode and in the constant light control function,
the lighting is switched on with the switch-on dimming value.
Value range (Glamox Sensor-app)
Switch on dimming value C1
30–100%
Configuration type C1
Value range (Glamox Sensor-app)
Fully automatic device: the lighting is switched on and off
automatically (based on presence, absence and brightness).
auto
Semi-automatic device: the lighting must always be switched
on manually. It is switched off automatically by the presence
detector (based on absence or brightness)
auto
IR group address C1
This parameter is applied when using the LMS MG USER
REMOTE or app remote control LMS MG PROGRAM REMOTE
BT.
A group address can be assigned to lighting channel C1. The
group addresses in the detector can be programmed with
the LMS MG PROGRAM REMOTE BT/App or LMS MG USER
REMOTE.
Value range
Adjustable values from LMS MG PROGRAM REMOTE BT
I, II, III
Adjustable values from LMS MG PROGRAM REMOTE BT/
App
I–VIII, all
Adjustable values from LMS MG USER REMOTE
I, II
With the LMS MG USER REMOTE, the group address can be
assigned as follows:
Press the and
buttons at the same time for at
least 5 s
I
Press the and
buttons at the same time for at
least 5 s
II
With the app remote control, the group address can be assig-
ned without the app as follows:
Press the and
buttons at the same time for at
least 5 s
I
Press button A and the
button at the same time for
at least 5 s
II
Press the and
buttons at the same time for at
least 5 s
III
Scene 1 C1/Scene 2 C1
The required dimming value for lighting channel C1 can be
assigned to scene 1 and scene 2.
Value range (Glamox Sensor-app)
Adjustable values
0–100 %