CFA-24V / CFA-230V INSTALLATION INSTRUCTIONS

ENGLISH

Electronic freeze protection alarm with 

warming function, double relays and digital 

display.

CFA-24V  Freeze protection alarm 24V AC
CFA-230V  Freeze protection alarm 230V AC

WARNING: IMPORTANT

INFORMATION

CONCERNING

ELECTRICAL SAFETY 

AND ENVIRONMENT

This product may contain dangerous volt-

age. The product’s housing is not meant 

to be removed. At a supply voltage of 

230V AC the product must be powered 

via a nearby mains switch labelled “Mains 

Switch for CFA freeze protection alarm”. 

The product’s relay switch can be powered 

with 230V. The power must be switched off 

during maintenance. The product is intend-

ed for indoor use only. The product must 

not be subjected to liquid or moisture. The  

product’s exterior can be cleaned using 

a damp cloth. The product is intended for 

mounting on a DIN rail / Norm enclosure in 

a protected space.

!

INDEX

1.  Technical Data
2. Function
3. Use
4. Installation
5. Maintenance
6.  Buttons and menu system
7.  Selection of temperature sensor type –  

factory setting: Pt1000

8.  Setting the setpoint
9.  Resetting the alarm
10.  Fine-adjustment of the temperature  

measurement

11.  Display example
12.  Error codes and temperature / Ohms table
13.  Figures
14.  Connection examples for CFA-24V and 

CFA-230V

15.  Menu system – monitoring / shortcut menu

1.  TECHNICAL DATA
Supply voltage

 

  CFA-24V:

 

24V AC ±10%, 

  CFA-230V:

 

230V AC ±10% 50-60 Hz

Relay outputs:

 250V 

~ 5 A resistive  

   

loading, potential-free  

  

changeover

Power consumption:  

4W

Output signal:  

0-10V or 10-0V

Temperature range 

  Alarm temperature:  

0 to 20°C

  Warming function:  

5 to 50°C

Ambient temp.:  

0 to +40°C

Selectable  

temperature sensor: 

Pt1000 (factory setting), 

   

NTC (Calectro type: 22/ 

   

33/44/55/99), Pt100,  

  

Ni1000,

 

and

 

PTC  

   

(Calectro type: 95)

Mounting:

 

DIN rail, Norm enclosure

Dimensions WxHxD:

  52.5 x 86 x 59 mm

Weight:

 

240 gram

Protection class:

 IP20

2. FUNCTION

CFA is connected to a temperature sensor that  

measures the water temperature in the heating 

coil. The water temperature in the heating coil is  

normally regulated by another regulator/DUC with the  

control signal (0-10 or 10-0V) connected via CFA to the  

control valve. If the water temperature in the coil 

drops without any response from the regulator / 

DUC, CFA starts regulating the control valve.
When the water temperature in the coil drops below 

the pre-set alarm temperature, both relay outlets fall 

(normally activated). 

Daytime mode

During daytime the control signal regulates with a 

proportional band of 4°C. The control signal begins 

regulating when the temperature drops to the pre-set 

alarm temperature plus one degree plus the 

 

proportional band.
Example 1: Alarm temperature = 5°C: The control 

signal begins regulating at 10°C (5+1+4).
Example 2: Alarm temperature = 5°C: At or under 

6°C the control signal is 100%.

Temperature

Control signal

Alarm temperature

0%

1°C

4°C p-band

100%

DAYTIME MODE

Daytime mode is activated by a short circuit 

between terminals 9 and 12. During daytime 

mode, D4 is shown in the top right-hand corner 

of the display and DI (under °C) is lit to indicate 

that the digital input (DI) is short-circuited.

Menu

°

C

DI

 

 



Night mode / warming function

During night mode (warming function) the water 

temperature in the heating coil is regulated by 

a setpoint that is adjustable between 5 and 50° 

(proportional band: 10°C).

Temperature

Control signal

alarm temperature

0%

10°C P-band

100%

NIGHT MODE

Warming function 

setpoint

Night mode is activated by cutting any jumpers 

between terminals 9 and 12.

Menu

°

C

 





Self-test

During start-up and the replacement of 

 

temperature sensors, CFA performs a self-test. 

Three lines begin to blink at the bottom of the  

display. The current temperature shows up here 

on completion. Interruption on the temperature 

sensor circuit shows up as Er0 on the display, 

and Er1 for short circuit. Upon interruption or 

short circuit, the alarm relays fall and the control 

signal goes to 100%.

3. USE

CFA is an electronic freeze protection alarm with 

a digital display that is used to monitor frost in 

air heating systems that use water as the heat  

carrier.

4. INSTALLATION

CFA is mounted on a DIN rail and is suited to 

Norm enclosures.

5. MAINTENANCE

CFA requires no maintenance.

© 2020.1

1.20  R1.1   Calectro 

AB   HFE656 EN

EN

Summary of Contents for CFA-24V

Page 1: ...r temperature in the heating coil is normally regulated by another regulator DUC with the controlsignal 0 10or10 0V connectedviaCFAtothe control valve If the water temperature in the coil drops without any response from the regulator DUC CFA starts regulating the control valve When the water temperature in the coil drops below the pre set alarm temperature both relay outlets fall normally activate...

Page 2: ... and PTC sensors in the ETF series Pt1000 is a factory set sensor 2 Press the Menu button to enter the menu system 3 The current type of temperature sensor is shown 4 Press Menu Enter to change the tempera ture sensor type 5 The current sensor type begins to blink and you can now use the arrow buttons to select another sensor type Press Enter to confirm your selection 6 Use the arrow keys and conf...

Page 3: ...2 Relay 2 Relay 2 1 2 L N 3 4 5 6 7 8 9 10 11 12 13 14 15 16 GND Temp sensor Temp sensor Digital in Analogue out Analogue in Not used Not used RC DUC FIG 3 CFA 230V The relay outputs are shown in alarm no power on condition Max 5A 250V 230V AC 230V AC Relay 1 Relay 1 Relay 1 Relay 2 Relay 2 Relay 2 1 2 L N 3 4 5 6 7 8 9 10 11 12 13 14 15 16 GND Temp sensor Temp sensor Digital in Analogue out Analo...

Page 4: ...gh Exit Menu Enter Select the desired output signal 0 10V or 10 0V Confirm with Enter Enter Ni 1000 C C Adj Menu Enter Enter Menu C DI Menu C DI Press Menu to access the Menu System Navigate between the submenus using the arrow keys and select sub menu with Menu Enter Select the type of temperature sensor Navigate between the different types and confirm with Enter If necessary the temperature meas...

Reviews: