Signet 8250-2 Level Transmitter 

5.3 Relay 

Operation

Relay outputs can be used as switches that respond when the 
process variables move above or below setpoints, or when the 
process variables move outside of a window.
•  The relays may be turned Off if not in use.
•  Response can be delayed up to 6400 s ( see Calibrate menu).

Low:

Relay is energized when process variable is less than the 
setpoint. The relay de-energizes when the process variable 
moves above the setpoint plus the hysteresis value.

High:

Relay is energized when process variable is greater than the 
setpoint. The relay de-energizes when the process variable 
moves below the setpoint plus the hysteresis value.

Window:

Relay is energized when the process variable moves above or 
below a 

fi

 xed window of values. The relay de-energizes when 

the process variable moves inside the window by more than the 
hysteresis value.

Note: 

Relays will operate in reverse if miswired. Observe relay 

logic appropriate to the application.

6. VIEW 

Menu

•  During normal operation, the ProcessPro displays the VIEW menu.
•  To select a display, press the UP or DOWN arrow keys. The display selections scroll in a continuous loop.
•  Changing the display selection does not interrupt system operations.
•  No keycode is necessary to change display selection.
•  Output settings cannot be edited from the VIEW menu.
•  When using the CALIBRATE or OPTIONS menus, the ProcessPro will return to the VIEW menu if no key 

is pressed for 10 minutes.

View Menu

Signet Level

Transmitter

Level

+10.00 ft

Relay 1 

Relay 2 

ENTER

Window

High Limit

Hysteresis

Hysteresis

Time

Low Limit

Process

Hysteresis 

Time 

Low Setpoint 

Process 

Relay energized

Relay de-energized

Hysteresis 

Time 

High Setpoint

Process

Display

Description

Level

+10.00  ft

Displays the Level value.
Permanent display when "Level" is the display selection in OPTIONS menu.

Volume

+30.00 gal

Displays the Volume value.
Permanent display when "Volume" is the display selection in OPTIONS menu.

LVL +10.00  ft

VOL +300.00 gal

Displays the Level and Volume simultaneously.
Permanent display when "Both" is the display selection in OPTIONS menu.

All of the displays below are temporary. After 10 minutes the display returns to the permanent display.

Loop Output:

12.00 mA

Monitor the 4 to 20 mA Loop output.

Relay A: On

Relay B: Off

Displays the status of Relays A and B. 
Appears only when external relay module is detected.

No Relay Module

Detected

Displayed if the relay module is not detected at Sensor Con

fi

 guration (see 

calibrate menu)

Note: When using the 8059-4 or -4AC, only relays 1 and 2 can be utilized 

with the level instrument.

Last CAL:

02-10-09

Monitor date for scheduled maintenance or date of last calibration.
(See description in Calibrate Menu.)

Summary of Contents for Signet 3-8250-2

Page 1: ...ble and reversible Max loop impedance 50 max 12 V 325 max 18 V 600 max 24 V Update rate 300 ms Output accuracy 0 03 mA Relay outputs 2 sets mechanical SPDT contacts Software supports 2 additional rela...

Page 2: ...ure instrument temporarily with tape from front or grip from rear of instrument DO NOT RELEASE 5 Press quick clips outward and remove 2 1 Terminals 11 13 Digital S3 L The 2450 sensor and External Rela...

Page 3: ...el 1 4 to 20 mA in Channel 2 4 to 20 mA in System Pwr Loop System Pwr Loop AUX Power AUX Power System Pwr Loop System Pwr Loop AUX Power AUX Power Loop Input 4 to 20 mA System Pwr Loop System Pwr Loop...

Page 4: ...menu if the sensor is located at Z Level L The distance from Z to surface of fluid displayed as Level by transmitter L 0 O 0 Z SLOC L 0 O 0 Z SLOC L 0 SLOC O 0 Z 2450 Pressure Sensor Location and Offs...

Page 5: ...ted at each transition point in the vessel shape for example at custom point 9 where the shape changes from a cylinder to a cone The more complex sections should be defined with more points Notice tha...

Page 6: ...to change display selection Output settings cannot be edited from the VIEW menu When using the CALIBRATE or OPTIONS menus the ProcessPro will return to the VIEW menu if no key is pressed for 10 minut...

Page 7: ...g Procedure Step 1 Press and hold ENTER key 2 seconds to select the CALIBRATE menu 5 seconds to select the OPTIONS menu Step 2 The Key Code is UP UP UP DOWN keys in sequence After entering the Key Cod...

Page 8: ...L Single point calibration for Level Reset LVL to Factory Cal Yes Reset Level to original factory calibration Set LVL entry is erased No Return to menu do not reset Level Loop Source LVL Select the so...

Page 9: ...for relay response Relay will be activated only if the source value exceeds the setpoint for this time period Relay settings will repeat for Relay 2 and for External Relays External Relays require th...

Page 10: ...t Test Relay 1 Press UP or DOWN keys to manually toggle the state of Relay 1 Display Factory settings shown Description VOL Shape Vert Cylinder Select the shape of the vessel where Sensor is located V...

Page 11: ...iew all custom points and reset values so each point is greater than the preceding point CHK SENSOR Problem with the sensor during different modes of operation 1 Wiring problem AUXILIARY POWER was not...

Page 12: ...upply Note When using the 8059 4 or 8059 4AC only relays 1 and 2 can be utilized with the flow instrument Accessories Mfr Part No Code Description 3 8050 159 000 184 Universal mounting kit 3 8050 395...

Reviews: