Signet 8250-2 Level Transmitter 

Terminals 5-10: Relay Outputs

Two sets mechanical SPDT contacts programmable as:

•  High or Low setpoint with adjustable hysteresis
•  "Window" limits with adjustable hysteresis
•  Time delay up to 6400 seconds.
•  May be disabled (Off) if not used.
•  Auxiliary power (terminals 1-2) MUST be connected 

for relay operation

Terminals 1 and 2: AUXILIARY power

Required for all systems that include relay 
operation.

 

13 

12 

11 

 

 

10 

AUX
Power +

Sensr Gnd 

(SHIELD) 

 

Sensr IN 

(RED) 

 

Sensr V+ 

(BLACK) 

Relay 2

(NO)

Relay 2

(COM)

Relay 2

(NC)

Relay 1

(NO)

Relay 1

(COM)

Relay 1

(NC)

System Pwr
Loop -

System Pwr
Loop +

AUX
Power -

3. Panel 

Installation

1.  The panel mount transmitter is designed for installation using a 1/4 DIN Punch. For 

manual panel cutout, an adhesive template is provided as an installation guide. The 
cutout must be 92 mm x 92 mm. Recommended clearance on all sides between 
instruments is 25 mm (1 in.)

2.  Slide the instrument into the cutout from the front of the panel.
3.  Slide the mounting bracket over back of instrument until quick-clips snap into latches on 

side of instrument.

4.  To remove, secure instrument temporarily with tape from front or grip from rear of 

instrument. DO NOT RELEASE.

5.  Press quick-clips outward and remove.

2

1

Terminals 11-13: Digital (S

3

L)

The 2450 sensor and External Relay 
Module connect here.

System Pwr
Loop -

System Pwr
Loop +

2

1

Sensr Gnd

(SHIELD)

Sensr IN

(RED)

Sensr V+

(BLACK)

7

6

5

4

3

AUX
Power -

AUX
Power +

13

12

11

Relay 2
(NO)

Relay 2
(NC)

10

9

8

Relay 2
(COM)

Relay 1
(NO)

Relay 1
(NC)

Relay 1
(COM)

quick-clips

gasket

panel

terminals

mounting

bracket

latch

Panel Mount
Installation Detail

4. Electrical 

Connections

CAUTION:

 Failure to fully open terminal jaws before removing wire may permanently damage instrument.

Wiring Procedure

  1.  Remove 13 mm - 16 mm (0.5 in. - 0.625 in.) of insulation from wire end.
  2.  Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
  3.  Insert exposed (non-insulated) wire end in terminal hole until it bottoms out. 
  4.  Release orange terminal lever to secure wire in place.  Gently pull on each wire to ensure a good connection.

Wiring Removal Procedure

  1.  Press the orange terminal lever downward with a small screwdriver to open terminal jaws.
  2.  When fully open, remove wire from terminal.

Terminals 3 and 4: Loop Power

12-24 VDC ±10% system power 

and current loop output.

Max. loop impedance:

  50 

Ω

 max. @ 12 V

325 

Ω

 max. @ 18 V

600 

Ω

 max. @ 24 V

Summary of Contents for Signet 3-8250-2

Page 1: ...ble and reversible Max loop impedance 50 max 12 V 325 max 18 V 600 max 24 V Update rate 300 ms Output accuracy 0 03 mA Relay outputs 2 sets mechanical SPDT contacts Software supports 2 additional rela...

Page 2: ...ure instrument temporarily with tape from front or grip from rear of instrument DO NOT RELEASE 5 Press quick clips outward and remove 2 1 Terminals 11 13 Digital S3 L The 2450 sensor and External Rela...

Page 3: ...el 1 4 to 20 mA in Channel 2 4 to 20 mA in System Pwr Loop System Pwr Loop AUX Power AUX Power System Pwr Loop System Pwr Loop AUX Power AUX Power Loop Input 4 to 20 mA System Pwr Loop System Pwr Loop...

Page 4: ...menu if the sensor is located at Z Level L The distance from Z to surface of fluid displayed as Level by transmitter L 0 O 0 Z SLOC L 0 O 0 Z SLOC L 0 SLOC O 0 Z 2450 Pressure Sensor Location and Offs...

Page 5: ...ted at each transition point in the vessel shape for example at custom point 9 where the shape changes from a cylinder to a cone The more complex sections should be defined with more points Notice tha...

Page 6: ...to change display selection Output settings cannot be edited from the VIEW menu When using the CALIBRATE or OPTIONS menus the ProcessPro will return to the VIEW menu if no key is pressed for 10 minut...

Page 7: ...g Procedure Step 1 Press and hold ENTER key 2 seconds to select the CALIBRATE menu 5 seconds to select the OPTIONS menu Step 2 The Key Code is UP UP UP DOWN keys in sequence After entering the Key Cod...

Page 8: ...L Single point calibration for Level Reset LVL to Factory Cal Yes Reset Level to original factory calibration Set LVL entry is erased No Return to menu do not reset Level Loop Source LVL Select the so...

Page 9: ...for relay response Relay will be activated only if the source value exceeds the setpoint for this time period Relay settings will repeat for Relay 2 and for External Relays External Relays require th...

Page 10: ...t Test Relay 1 Press UP or DOWN keys to manually toggle the state of Relay 1 Display Factory settings shown Description VOL Shape Vert Cylinder Select the shape of the vessel where Sensor is located V...

Page 11: ...iew all custom points and reset values so each point is greater than the preceding point CHK SENSOR Problem with the sensor during different modes of operation 1 Wiring problem AUXILIARY POWER was not...

Page 12: ...upply Note When using the 8059 4 or 8059 4AC only relays 1 and 2 can be utilized with the flow instrument Accessories Mfr Part No Code Description 3 8050 159 000 184 Universal mounting kit 3 8050 395...

Reviews: