Signet 8250-2 Level Transmitter

8. Calibrate 

Menu 

(continued)

Display

(Factory settings shown)

Description

The Relay settings below will not appear if the Relay mode is OFF.

Relay 1 Source:

LVL >

Select the source for Relay: LVL or VOL.

Relay 1 Setpnt:

+0.0000 ft 

>

If Relay is in Low or High mode, the relay will be energized when the level or volume reaches 
this value.

Relay 1 Rng: ft

+0.0000 

 +10.000  >

If Relay is in Window mode, the relay will be energized when the level or volume is less than 
(low limit) or greater than (hig limit) the range. You must enter the low limit into the 

fi

 rst 

fi

 eld, 

and the high limit into the second 

fi

 eld.

Relay 1 Hys:

0.00 ft 

>

Relay will be de-energized at Setpoint ± Hysteresis.
The Hysteresis value is in Level units or % of full scale.

Relay 1 Delay:

0.0 secs 

>

Set up to 6400 seconds delay time for relay response.
Relay will be activated only if the source value exceeds the setpoint for this time period.

• 

Relay settings will repeat for Relay #2 and for External Relays.

• 

External Relays require the optional External Relay Module (model number 3-8059-4 or 3-8059-4AC).

• 

Note: When using the 8059-4 or -4AC, only relays 1 and 2 can be utilized with the fl ow instrument.

Reset Sensor

Con

fi

 guration: >

Use this function during initial startup of a new system, and whenever a new sensor is added 
to the system. It enables the 8250 to scan the sensor input terminals and determine the type 
and speci

fi

 c serial numbers of the sensors connected to the sensor input.

Last CAL:

2-10-09

Use this “note pad” to record important dates, such as annual recerti

fi

 cation or scheduled 

maintenance.

Technical Note

If you see this error

during normal operation

The most likely cause is

Remedy

CHK SENSOR

A new sensor was connected to the 8250 
but the "Sensor Reset Con

fi

 guration" has 

not been executed.

Perform the sensor con

fi

 guration.

*

Summary of Contents for Signet 3-8250-2

Page 1: ...ble and reversible Max loop impedance 50 max 12 V 325 max 18 V 600 max 24 V Update rate 300 ms Output accuracy 0 03 mA Relay outputs 2 sets mechanical SPDT contacts Software supports 2 additional rela...

Page 2: ...ure instrument temporarily with tape from front or grip from rear of instrument DO NOT RELEASE 5 Press quick clips outward and remove 2 1 Terminals 11 13 Digital S3 L The 2450 sensor and External Rela...

Page 3: ...el 1 4 to 20 mA in Channel 2 4 to 20 mA in System Pwr Loop System Pwr Loop AUX Power AUX Power System Pwr Loop System Pwr Loop AUX Power AUX Power Loop Input 4 to 20 mA System Pwr Loop System Pwr Loop...

Page 4: ...menu if the sensor is located at Z Level L The distance from Z to surface of fluid displayed as Level by transmitter L 0 O 0 Z SLOC L 0 O 0 Z SLOC L 0 SLOC O 0 Z 2450 Pressure Sensor Location and Offs...

Page 5: ...ted at each transition point in the vessel shape for example at custom point 9 where the shape changes from a cylinder to a cone The more complex sections should be defined with more points Notice tha...

Page 6: ...to change display selection Output settings cannot be edited from the VIEW menu When using the CALIBRATE or OPTIONS menus the ProcessPro will return to the VIEW menu if no key is pressed for 10 minut...

Page 7: ...g Procedure Step 1 Press and hold ENTER key 2 seconds to select the CALIBRATE menu 5 seconds to select the OPTIONS menu Step 2 The Key Code is UP UP UP DOWN keys in sequence After entering the Key Cod...

Page 8: ...L Single point calibration for Level Reset LVL to Factory Cal Yes Reset Level to original factory calibration Set LVL entry is erased No Return to menu do not reset Level Loop Source LVL Select the so...

Page 9: ...for relay response Relay will be activated only if the source value exceeds the setpoint for this time period Relay settings will repeat for Relay 2 and for External Relays External Relays require th...

Page 10: ...t Test Relay 1 Press UP or DOWN keys to manually toggle the state of Relay 1 Display Factory settings shown Description VOL Shape Vert Cylinder Select the shape of the vessel where Sensor is located V...

Page 11: ...iew all custom points and reset values so each point is greater than the preceding point CHK SENSOR Problem with the sensor during different modes of operation 1 Wiring problem AUXILIARY POWER was not...

Page 12: ...upply Note When using the 8059 4 or 8059 4AC only relays 1 and 2 can be utilized with the flow instrument Accessories Mfr Part No Code Description 3 8050 159 000 184 Universal mounting kit 3 8050 395...

Reviews: