11

Signet 8250-2 Level Transmitter

10. Troubleshooting

Display Condition

Possible Causes

Suggested Solutions

Value must be 6400 or less

Time delay cannot be greater than 6400 s.

Set time delay to 6400 s or less.

Value must be more than zero

Speci

fi

 c gravity value set to 0.0000

Set speci

fi

 c gravity to a value greater than 0.

Must have more than 1 point
Must have 10 or less points

Custom Shape requires from 3 to 10 
custom points.

Enter 3 to 10 custom points.

Must be > than previous point

A custom point has been entered that is not 
greater than the previous point.
(Custom points must be in ascending 
order.)

Reset the custom point to a value greater 
than the preceding point.

CustomTable Error

Number of custom points increased without 
setting new values so all custom points are 
not sequential.

Review all custom points and reset values 
so each point is greater than the preceding 
point.

CHK SENSOR

Problem with the sensor during different 
modes of operation:
1. Wiring problem:

•  AUXILIARY POWER was not 

connected when LOOP power started.

•  The sensor is not connected properly.
•  The sensor cable is detached.

2.  The sensor has not been con

fi

 gured.

3.  The sensor is defective.

1.  Start AUX power, then LOOP power.
2.  Check sensor wiring.
3.  Perform SENSOR CONFIGURATION in 

CALIBRATE menu.

4.  Replace the sensor, then perform 

SENSOR CONFIGURATION.

Too Much Error

Check Sensor

0 SENR(S) FOUND: SAVE ?

No Relay Module Found

•  External Relay Module wiring is loose.
•  Relay module has been disconnected.
•  Relay module has been replaced.
•  Relay module is defective.

1. Check wiring
2.  Reset SENSOR CONFIGURATION
3.  Replace External Relay Module.

• 

External Relays require the optional External Relay Module (model number 3-8059-4 or 3-8059-4AC).

• 

Note: When using the 8059-4 or -4AC, only relays 1 and 2 can be utilized with the fl ow instrument.

Summary of Contents for Signet 3-8250-2

Page 1: ...ble and reversible Max loop impedance 50 max 12 V 325 max 18 V 600 max 24 V Update rate 300 ms Output accuracy 0 03 mA Relay outputs 2 sets mechanical SPDT contacts Software supports 2 additional rela...

Page 2: ...ure instrument temporarily with tape from front or grip from rear of instrument DO NOT RELEASE 5 Press quick clips outward and remove 2 1 Terminals 11 13 Digital S3 L The 2450 sensor and External Rela...

Page 3: ...el 1 4 to 20 mA in Channel 2 4 to 20 mA in System Pwr Loop System Pwr Loop AUX Power AUX Power System Pwr Loop System Pwr Loop AUX Power AUX Power Loop Input 4 to 20 mA System Pwr Loop System Pwr Loop...

Page 4: ...menu if the sensor is located at Z Level L The distance from Z to surface of fluid displayed as Level by transmitter L 0 O 0 Z SLOC L 0 O 0 Z SLOC L 0 SLOC O 0 Z 2450 Pressure Sensor Location and Offs...

Page 5: ...ted at each transition point in the vessel shape for example at custom point 9 where the shape changes from a cylinder to a cone The more complex sections should be defined with more points Notice tha...

Page 6: ...to change display selection Output settings cannot be edited from the VIEW menu When using the CALIBRATE or OPTIONS menus the ProcessPro will return to the VIEW menu if no key is pressed for 10 minut...

Page 7: ...g Procedure Step 1 Press and hold ENTER key 2 seconds to select the CALIBRATE menu 5 seconds to select the OPTIONS menu Step 2 The Key Code is UP UP UP DOWN keys in sequence After entering the Key Cod...

Page 8: ...L Single point calibration for Level Reset LVL to Factory Cal Yes Reset Level to original factory calibration Set LVL entry is erased No Return to menu do not reset Level Loop Source LVL Select the so...

Page 9: ...for relay response Relay will be activated only if the source value exceeds the setpoint for this time period Relay settings will repeat for Relay 2 and for External Relays External Relays require th...

Page 10: ...t Test Relay 1 Press UP or DOWN keys to manually toggle the state of Relay 1 Display Factory settings shown Description VOL Shape Vert Cylinder Select the shape of the vessel where Sensor is located V...

Page 11: ...iew all custom points and reset values so each point is greater than the preceding point CHK SENSOR Problem with the sensor during different modes of operation 1 Wiring problem AUXILIARY POWER was not...

Page 12: ...upply Note When using the 8059 4 or 8059 4AC only relays 1 and 2 can be utilized with the flow instrument Accessories Mfr Part No Code Description 3 8050 159 000 184 Universal mounting kit 3 8050 395...

Reviews: