SECULOGIC TZ300
34
Wiring diagram
IQ Lock EM, lever locks
6.9
IQ Lock EM power from TZ300
6.9.1
For connecting the IQ Lock EM, relay card RP220 is required in addition.
X100 (red terminal strip)
Supply GND
24 V DC supply
Power supply unit
Screw terminal
Relay card RP220
Nr. 102355
Door contact
L
Locking -
Door locked
24 V DC
Door closed
Brief unlocking input
24 V DC
Emergencyunlockinginput
24 V DC
X101 (orange terminal strip)
Caution: Order of terminals not as
on terminal strip
X102 (blue terminal strip)
Temporary unlocking through:
- External key switch
- Access control
- Button, etc.
Floating NO contact required
Lock connection cable
red wire
black wire
Magnet -
red/blue wire
COM cylinder contact
grey/pink wire NO cylinder contact
Caution: Sever red wire jumper (1–7)
behind terminal field of
FTÖ331U
Function:
When the TZ300 is locked, the outer lever handle of the IQ Lock EM is disengaged.
When the TZ300 is temporarily or permanently unlocked, the outer lever handle is engaged.
Option 1:
When the cylinder contact of IQ Lock is connected to the Temporary Unlocking input, cylinder operation
through the key triggers temporary unlocking.
At the same time, the TZ300 engages the outer lever handle.
*) Observe total power consumption of the TZ300.
If necessary, use a separate power supply unit.