![GEZE SecuLogic RWS TZ 300 Installation And Commissioning Instructions With Wiring Diagram Download Page 31](http://html1.mh-extra.com/html/geze/seculogic-rws-tz-300/seculogic-rws-tz-300_installation-and-commissioning-instructions-with-wiring-diagram_2219068031.webp)
SECULOGIC TZ300
31
Wiring diagram
Key switch with indicator SCT222
6.6.6
For connecting the SCT222, relay card RP220 is required in addition.
red terminal strip
Supply GND
24 V DC supply
Power supply unit
Screw terminal
Door contact
Caution: Sever red wire jumper
(1–7) behind terminal
field of FTÖ331U
L
Locking -
Door locked
24 V DC
Door closed
Brief unlocking input
24 V DC
Emergencyunlockinginput
24 V DC
orange terminal strip
Caution: Order of terminals not as
on terminal strip
blue terminal strip
24 V DC
Alarm
output
max. 1 A,
24 V DC
Plug for GEZE
key switch
Ribbon cable
Connection
to TST300
Key switch
24 V DC
Lock SCT, KZF, acknowledge
Unlock SCT, acknowledge
Tamper
SCT222 UP No. 100064
SCT222 AP No. 100065
green-red LED
yellow LED
right contact
left contact
Relay card RP220
Nr. 102355
For notes about the wiring diagram, see section 6.4.2