GEZE SecuLogic RWS TZ 300 Installation And Commissioning Instructions With Wiring Diagram Download Page 12

SECULOGIC TZ300

12

Commissioning

Commissioning

Preconditions 

4.1 

Doors with electrical locks along escape routes must be taken into operation after the manufacturer has certified 
their suitability for the intended purpose.  In addition, the correct installation and correct function of the electri-
cal lock must be verified by a specialist.

Tamper switch TST300 

4.1.1 

When operating voltage is applied to the TZ300, a tamper alarm is triggered if the emergency button’s hood is 
not fitted.

Tamper switch SCT320 (on UP only)

4.1.2 

When operating voltage is applied to the TZ300, a tamper alarm is triggered if the emergency button’s hood is 
not fitted. If the tamper switch of the key switch is not to be evaluated, you must fit a jumper between terminals 
2 and 54. 

Disabling the tamper alarm

4.1.3 

For maintenance, the tamper alarm can be disabled for a limited time. To do this, turn the built-in key switch to 
the left for about ten seconds. This disables the tamper alarm for about two minutes. While it is disabled, the 
right LED is lit green and the left LED is off.
To reenable the tamper alarm before the two minutes are up, turn the built-in key switch to the right. The door 
control unit is then unlocked. To lock it, turn the key switch to the right again.

Settings

4.2 

 

No settings can be made or changed on the door control unit. All values, such as short-term release, cancelling, 
pre-alarm, etc. are permanently set.

Description of basic functions

4.3 

Short-term release (KZF)

4.3.1 

Short-term release releases the emergency door protection for a limited time.  During this time, access through 
the door is possible without triggering an alarm. It is activated with the built-in key switch or an external actuator 
connected to the short-term release input. 
The short-term release duration is about 20 seconds.

Cancellation of short-term release

4.3.2 

When short-term release is active, the door locks prematurely when it is closed before the short-term release 
time has expired. This prevents unauthorized access through the door after an authorized person has gone 
through. 

Retriggering on short-term release

4.3.3 

If the short-term release function is triggered again while the function is still active, the short-term release period 
starts again.

Pre-alarm

4.3.4 

If the door is passed through after the short-term release time has expired, an audible signal is issued to warn 
the user that the short-term release time has expired. The pre-alarm duration is 60 seconds. If the door is closed 
while a pre-alarm is active, the door is locked again automatically and the pre-alarm is reset.

Summary of Contents for SecuLogic RWS TZ 300

Page 1: ...1 GEZE SECULOGIC TZ300 Emergency Exit System Door Control Unit EN Installation and Commissioning Instructions with Wiring Diagram...

Page 2: ...2 4 1 Preconditions 12 4 2 Settings 12 4 3 Description of basic functions 12 4 4 Fire detection system BMA hazard alert system GMA smoke and heat extraction system RWA 13 5 Operation 14 5 1 Controllin...

Page 3: ...al ling interface to the building services management system Built in buzzers and LEDs provide visual and audible indication when an alarm has been triggered Related documents 1 2 All components are s...

Page 4: ...lock KZF Short term release MA500 Holding magnet NC Floating NC normally closed contact NO Floating NO normally open contact NOT320 Emergency button PSU Power supply unit OKFF Upper edge of finished...

Page 5: ...ion of the emergency exit system for visible damage and X X faults by the owner Any identified damage or faults must be rectified immediately by a GEZE service technici an or a GEZE authorized service...

Page 6: ...ds VDE 0100 und VDE 0815 for laying cables Tamper proof cable routing according to VDE 0833 surface mounted cables in steel conduit For flush mounted cabling flush mounted sockets depth 62 5 mm at a m...

Page 7: ...mains cable and ribbon cable in the flush mounted sockets X X Connect cable to terminal blocks according to wiring diagram X X 850 1200 60 71 71 6 2 5 Connect and fit the PSU X X Connect the key switc...

Page 8: ...LOGIC TZ300 8 Installation and assembly Fit the terminal blocks to the back of the door control unit X X C C D D Fit the door control unit X X Fit the green adhesive frame X X Test the unit s function...

Page 9: ...SECULOGIC TZ300 9 Installation and assembly Fitting the surface mounted door control unit 3 3 1 2 Door control unit TZ300SN 1 Terminal blocks 2 Open the housing X X...

Page 10: ...e to terminal blocks according to wiring diagram X X Fit the terminal blocks to the back of the door control unit X X Secure loose cables with cable ties X X Hook in housing and secure with screws X X...

Page 11: ...Release cap screw and remove the lock cylinder X X Fitting a safety cylinder length 40 10 3 5 If using a safety cylinder with 50 mm 40 10 use the spacers between key switch and housing Fit the spacer...

Page 12: ...is then unlocked To lock it turn the key switch to the right again Settings 4 2 No settings can be made or changed on the door control unit All values such as short term release cancelling pre alarm e...

Page 13: ...A hazard alert system GMA smoke and heat 4 4 extraction system RWA Alarm triggers 4 4 1 If the BMA GMA or RWA signal of a door control unit is applied it is unlocked and a local alarm is triggered aud...

Page 14: ...rol unit with emergency button 3 Locked LED 1 Door state LED 2 Alarm LED 3 No Indicator Colour Meaning 1 Red Locked Green Unlocked Green flashing every second Short term release 2 Red Door closed Gree...

Page 15: ...an be opened Turn the key to the left and hold it for about one second X X 1 2 3 LED 1 lights up green The door is unlocked Locking the door When the system is unlocked the locking elements are enable...

Page 16: ...tive the short term release period starts again is retriggered Precondition The door is locked Turn the key to the right X X 2 3 1 LED 1 flashes green The door remains unlocked for the set period of 2...

Page 17: ...econdition The alarm cause has been eliminated To acknowledge the alarm and lock the door Turn the key to the right X X To acknowledge the alarm and unlock the door Turn the key to the left X X The do...

Page 18: ...arm Alarm LED Alarm bell Pre alarm Yellow flashing light 1 s on 1 s off Acoustic signal 2 beeps Door alarm Yellow continuous light Acoustic signal 2 seconds continuous Tamper alarm Yellow continuous l...

Page 19: ...X and 10 Locking element connected with reversed polarity Emergency button LED goes on and off Other LEDs remain off With PSUs NET220 und NT19 2 24 With larger PSUs the fuse blows Immediately isolate...

Page 20: ...90 Alarm bell with flashlight 110 Holding magnet MA500 250 Alarm bell SLE220 16 Emergency exit door opener FT 331 160 Key switch with LED SCT222 30 Emergency exit door opener FT 332 105 Relay card RP2...

Page 21: ...ernal devices with standard PSU of the TZ300 UP NET220 max 350 mA AP NT19 2 24 max 650 mA with external PSU max 800 mA use only GEZE approved PSUs Terminal assignment Max cable cross section for screw...

Page 22: ...ernally 3 TZ300SN UP Protection class II PE protective earth conductor is not connected TZ300SN AP Protection class I with PE conductor testing according to VDE0100 4 In delivery state the 2K resistor...

Page 23: ...SECULOGIC TZ300 23 Wiring diagram Door control unit TZ300S TZ300SN 6 4 3 blue For notes about the wiring diagram see section 6 4 2...

Page 24: ...blue X100 red 24 V DC Lock SCT KZF acknowledge Unlock SCT acknowledge Tamper GEZE SCT320 Key switch TST300 Connection to TST300 X103 Plug for GEZE key switch X102 or X103 Ribbon cable X100 red termin...

Page 25: ...SECULOGIC TZ300 25 Wiring diagram Emergency unlocking through BMA GMA or RWA 6 4 5 For notes about the wiring diagram see section 6 4 2...

Page 26: ...l cables in series Programming interface red blue Holding magnet MA500 single leaf doors 6 5 1 TST300 X101 orange terminal strip Door contact Locking Locking Door locked 24 V DC Door closed 24 V DC Ho...

Page 27: ...minal strip 5 14 6 15 2 2 8 7 6 FT 331U 5 4 3 NO COM NC NO COM NC AKRR RR 2 8 7 6 FT 331U 5 4 3 NO COM NC NO COM NC AKRR RR A B A B 1 1 Locking Locking Door locked 24 V DC Door closed Caution Sever re...

Page 28: ...ocking Door locked 24 V DC Door closed Emergency door opener TYP331 DIN left two leaf doors 6 5 7 X101 orange terminal strip 5 14 6 15 2 2 4 5 6 RD GN BU NO COM NC NO COM NC AKRR RR NO COM NC NO COM N...

Page 29: ...WW No 094012 UP GIRA E2 pure white Closed on right Closed on left COM Key switch SCT221 SCT to short term release 6 6 3 Brief unlocking input 24 V DC orange terminal strip No 094170 UP Jung LS990 stai...

Page 30: ...ledge Unlock SCT acknowledge Tamper key switch No 132278 UP GIRA E2 anthracite No 130370 UP GIRA E2 pure white No 131984 UP Jung AS500 WW Key switch SCT220 for external control 6 6 5 unlocking locking...

Page 31: ...ked 24 V DC Door closed Brief unlocking input 24 V DC Emergencyunlockinginput 24 V DC orange terminal strip Caution Order of terminals not as on terminal strip blue terminal strip 24 V DC Alarm output...

Page 32: ...cal code lock Toplock CTI CTI B 6 7 1 X102 blue or X100 red X101 orange terminal strip Brief unlocking input Numerical codelock Toplock CTS V CTS BV 6 7 2 Number codelock Toplock CTS V CTS BV Brief un...

Page 33: ...V DC orange terminal strip Optionally the GCDU100 can be supplied with power through the TZ300 Observe total power consumption Supply GND 24 V DC supply X100 red terminal strip Timer 6 8 Brief unlock...

Page 34: ...key switch Access control Button etc Floating NO contact required Lock connection cable red wire Magnet black wire Magnet red blue wire COM cylinder contact grey pink wire NO cylinder contact Caution...

Page 35: ...he outer lever handle of the IQ Lock EM is disengaged When the TZ300 is temporarily or permanently unlocked the outer lever handle is engaged Option 1 When the cylinder contact of IQ Lock is connected...

Page 36: ...ergency button illumination working Emergency button function OK Tamper switches working correctly Unlocking through key switch is working correctly Locking through key switch is working correctly Fee...

Page 37: ...0 seconds If the door is closed while a pre alarm is active the door is locked automatically and the pre alarm is reset Door alarm If the pre alarm time is exceeded the door alarm is triggered This mu...

Page 38: ...voltage 24 V DC 10 Power consumption 100 mA at 24 V DC w o peripherals Total power consumption 1 A at 24 V DC depending on PSU used Protection class II according to EN 60950 in built in state Mountin...

Page 39: ...w o peripherals Total power consumption Versions with PSU 800 mA Versions without PSU Max 1A depending on PSU used Protection class Versions with PSU I according to EN 60950 Versions without PSU II a...

Page 40: ...0 to 50 C Package content Emergency exit sign module green border Key switch SCT320UP 7 3 4 Technical specifications Device name Key switch SCT320UP Versions White Anthracite Pure white Function Key s...

Page 41: ...SECULOGIC TZ300 41...

Page 42: ...SECULOGIC TZ300 42...

Page 43: ...SECULOGIC TZ300 43...

Page 44: ...est H 1115 Tel 36 1 481 4670 Fax 36 1 481 4671 E Mail office hungary geze com Iberia GEZE Iberia S R L Pol Ind El Pla C Comerc 2 22 Nave 12 08980 Sant Feliu de Llobregat Barcelona Tel 34 0 9 02194036...

Reviews: