SECULOGIC TZ300
19
Operation
Removing alarms and system faults
5.5
Alarm state
Cause of alarm
Elimination of alarm cause
Pre-alarm
Door not closed after unlocking period has expired.
No closed signal
Close door.
X
Unlock door.
X
Door alarm
No closed signal
Close door.
X
Check door contact.
X
No locked signal
Check locking element.
X
Tamper alarm
Tamper switch of door control unit not
closed (on UP only).
Close contact.
X
Fit cover.
X
After suppression time,acknowledge
X
alarm.
Key switch tamper switch not closed.
Alarm
Emergency button of TZ300 pressed
(direct unlocking).
Reset door control unit emergency
X
button.
Fuse in TST300 blown.
Check fuse.
X
Replace fuse.
X
Emergency unlocking through connected BMA,
GMA or RWA.
Check BMA, GMA or RWA and switch
X
off emergency unlocking signal.
Check input of affected door control
X
unit.
2K resistor between terminals 2 and 10 not set and
no BMA, GMA or RWA connected.
Fit a 2K resistor between terminals 2
X
and 10.
Locking element connected with reversed polarity.
Emergency button LED goes on and off. Other LEDs
remain off. (With PSUs NET220 und NT19.2-24. With
larger PSUs the fuse blows.)
Immediately isolate from the power
X
supply and connect correctly.
Locking element not connected.
Connect locking element.
X
Jumper on FTÖ331U was not removed.
FTÖ332 is connected without RP220.
Short-circuit in the supply line of the lockingele-
ment.
Remove jumper on FTÖ331.
X
Check locking element supply line for
X
short-circuit.
Connect FTÖ332 with RP220.
X
Press emergency button.
X
Release (pull out) emergency button.
X
Controller defective
Replace door control unit.
X
When the alarm cause has been remedied, the alarm must be acknowledged with the built-in key switch.
Mains failure
5.6
When mains power is restored, the door control unit is always in operating state Locked.
If an alarm is active when mains power is restored, the door control unit is in operating state Alarm.
Operating mode before mains failure
Operating mode after mains failure
Locked
Locked
Permanent unlocking
Locked
Short-term release
Locked
Alarm
Alarm or acknowledge alarm if cause no longer exists