ECturn/ECturn Inside
41
Error messages
22 Error messages
DPS
TPS
Service LEDs Error
group
Cause
Behaviour of the drive
5 4 3 2 1
–
○ ○ ○
○
○ ○ ○ ○ ○ ○
Operating
voltage
Drive is switched off.
○ ○ ○
○
○
x x x x x 24V
Short-circuit of the 24 V
Drive remains in operation. The 24V
LED on the control unit is off. Activa-
tion is not possible. TPS is off.
0 3
● ● ○
○
○
*
○ ○ ○ ●
Failure
supply
voltage
Failure of the on-site supply
voltage
If there is no rechargeable battery
available:
Leaf is braked by motor short-circuit.
If there is a rechargeable battery
available:
Behaviour depends on the setting
of the parameter AC (power failure).
The position is unknown after the
power has returned.
1 0
○ ○ ●
●
●
*
● ○ ● ○
Motor
rotary
encoder
No pulse from the rotary en-
coder despite motor current.
One of the two signals from
the incremental rotary en-
coder is missing.
The direction of rotation
does not correspond to the
set direction of rotation
of the motor.
Door leaf is braked by the motor and
the drive test is carried out.
Retests after every change in mode
of operation or after every activation.
If the rotary encoder is OK again,
the error is deleted.
11
○ ○ ●
●
●
*
● ○ ● ○
Motor
short-
circuit
Motor short-circuit.
Door leaf is braked by the motor.
Motor relay is opened.
Retests after every change in mode
of operation or after every activation.
If the motor is OK again, the error
is deleted and motor relay is closed
again.
1 2
○ ○ ●
●
●
*
● ○ ● ○
Motor
No motor current is meas-
ured although current is
supplied to the motor
Door leaf is braked by the motor.
Motor relay is opened.
Retests after every change in mode
of operation or after every activation.
1 3
○ ○ ●
●
○
*
○ ○ ● ●
Safety
sensor
close
Testing safety sensor close
is faulty
Retests 3 times in the open position.
Door closes with reduced speed.
Retests 10 times in the closing position.
Retests after every change in mode
of operation or after every activation.
As long as the error is active, the
door is only accessible manually.
Activation longer than 4 min Door closes slowly. As soon as the
signal is inactive again, the error
is deleted.
1 5
Display
pro-
gramme
switch
Monitoring only if DPS was
connected to the control unit
when the operating voltage
was switched on.
Drive remains in operation.
The error is deleted as soon as the
DPS responds again.
17
● ● ●
○
○
*
● ○ ○ ●
Electric
strike,
motor lock
An obstruction is recognised
in the closing position during
an attempt to open.
The door remains closed after
a further attempt to open.
Waiting for the next activation.
2 8
● ● ○
○
●
*
○ ● ● ●
Control
unit motor
relay
Testing the motor relay has
failed.
Internal error
OFF mode of operation
Position unknown