![GEZE ECturn Wiring Diagram Download Page 23](http://html.mh-extra.com/html/geze/ecturn/ecturn_wiring-diagram_2219106023.webp)
ECturn/ECturn Inside
23
WC control
12.3.1 24 V DC electric strike supplied on drive side
X
Attach free swing diode 1N4007 (mat. no. 115293)
to the electric strike.
GND
1
56
PA1B
55
PA1A
PA
24VTOE
5
1
1
Free swing diode
12.3.2 AC electric strike supplied on site
AC
1
GND
56 PA1B
55 PA1A
PA
24VTOE
5
AC
1
1
On-site AC power supply
12.4 Further functions
The set mode of operation or door mode can be signalled to a higher-level control unit or a building control
centre, see chapter 21, “Parameter menu”, via the configurable output PA1.
X
Set the parameters:
à
Set
a1
(configurable output) to the required signal (
0 4
…
1 2
).
12.5 WC control
See chapter 13.
13 WC control
Accessories:
à
GC 306 non-contact push button, mat. no. 163028
à
GC 306 non-contact push button with hand pictogram, mat. no. 163029
à
Plastic elbow switch, white, mat. no. 114078
à
Plastic elbow switch, stainless steel, mat. no. 114077
à
Stainless steel elbow switch, mat. no. 119898
à
LS 990 stainless steel elbow switch, surface-mounted, mat. no. 128582
à
LS 990 stainless steel elbow switch, flush-mounted, mat. no. 128583
à
SLE220 indicator lamp, flush-mounted, AS500, AW, mat. no. 115934
For the emergency shut-off switch, see chapter 6.1, “Key switch”.
Only operates with fail-safe electric strike. For connection and parameter setting of the electric strike, see