ECturn/ECturn Inside
22
Programmable output
11.8 Contact sensor K/DO mode of operation
The function depends on the duration of the signal at the PE input.
à
If the signal is active for less than 5 s, the function is the same as that of the contact sensor input K.
à
If the signal in the mode of operation is active for longer than 5 s, the control unit changes to DO mode of op-
eration. After the next short signal at the PE input, the control unit changes back to the AU mode of operation.
X
Set the parameters:
à
Set
e1
or
e2
(configurable input) to
11
for the “contact
sensor K/DO mode of operation” function.
ECturn
ECturn Inside
51 PE1
1
GND
2 24V
PE
52 PE2
2
24V
PE
11.9 WC control
See chapter 13, “WC control”.
12 Programmable output
à
PA is a potential-free relay contact, switching voltage/current max. 24 V AC/DC, 0.5 A.
à
The function of the configurable output PA can be selected via the service menu (see chapter 21, “Parameter menu”).
12.1 Gong
X
Set the parameters:
à
Set
a1
(configurable output) to
01
for the
“gong” function.
à
The contact closes for 1 s in the AU or DO mode
of operation as soon as contact sensor K or
radio channel FK1 or SIS and K are activated
55
PA1A
56
PA1B
PA
GONG
1
2
1
Gong transformer
2
Power supply circuit
12.2 Fault
X
Set the parameters:
à
Set
a1
(configurable output) to
0 2
for the
“fault” function.
à
The output contact closes as soon as the
control unit detects a system fault. At the same
time, the corresponding error number is indi-
cated at the TPS, DPS and at the service LEDs.
PA
55
PA1A
56
PA1B
1
GND
5
24VTOE
12.3 Electric strike and motor lock
à
A fail-secure electric strike, a fail-safe electric strike or a motor lock can be connected as an electric strike.
In addition, close pressure can be configured before opening in order to take the strain off the electric strike.
X
Set the parameters:
à
TO
(electric strike) to the required electric strike type with close pressure before opening if appropriate.
à
a1
(configurable output) to
0 3
for the “electric strike” function.
à
Activation of the electric strike is limited to 8 s plus the parametrised opening delay
a I
.
à
Connection of a lock feedback signal contact: see chapter 11.5, “Bolt message”
.