fu-processx-en 19
www.georgin.com
Instruction manual - ProcessX
Manifold
Impulse pipe
Isolating valve
Process pipe
Orifice plate
Impulse pipe
Manifold
isolating valve
Differential pressure source (orifice)
Process pipe
Isolating valve Process pipe
condensate
chamber
Manifold
Impulse pipe
5HFRPPDQGDWLRQIRUSURFHVVFRQQHFWLRQ
*DVÀRZPHDVXUHPHQW
Place the transmitter above the process pipe. If the pro-
cess temperature is high, please use a condensate cham-
ber like for steam
6WHDPÀRZPHDVXUHPHQW
Set two condensers at the same height between the
transmitter and the primary element.
Fill the pipe between the condensers and transmitter with
water.
Installation of a drain is necessary
/LTXLGÀRZPHDVXUHPHQWLQFDVHRIOLTXLG
Place the transmitter below the process pipe
Make piping so that gas in the impulse pipe is not
delivered to the transmitter, and incorporate gas res-
ervoirs as required..
3RVLWLRQRISURFHVVFRQQHFWLRQ
The position of the process connection is determined by the relationship between the condi-
WLRQFKDUDFWHULVWLFVDQGPHDVXULQJSRLQWRIWKHSURFHVVÀXLG
Follow the process position according to the process :
Gas measurement
Liquid measurement
Steam measurement
Upper
Lower
Upper
Lower
0 to 45° up from
the vertical
0 to 45° up from
the vertical
0 to 45° down from
the vertical