fu-processx-en 13
www.georgin.com
Instruction manual - ProcessX
INSTALLATION AND PIPING
Type Ambient
Process
Span
Static
Technical
temperature
temperature
limit
pressure
datasheets
limit
limit
limit
Differential
-40 to 85°C
-40 to 120°C
10 mbar
-1 to 32 bar
pressure
(silicone oil)
60 mbar
-1 to 100 bar
320 mbar
-1 to 160 bar
-20 to 80°C
(option : 420 bar)
EDSF6-134
ÀXRULQDWHGRLO PEDU
WREDU
(option : 420 bar)
5 bar
-1 to 160 bar
(option : 420 bar)
30 bar
-1 to 160 bar
(option : 300 bar)
200 bar
-1 to 300 bar
Gauge
-40 to 85°C
-40 to 100°C
1,3 bar
1,3 bar
Pressure
(silicone oil)
5 bar
5 bar
EDSF5-92
30 bar
30 bar
and
-20 to 80°C
100 bar
100 bar
EDSF5-98
ÀXRULQDWHGRLO EDU
EDU
Absolute
-40 to 85°C
-40 to 85°C
0,16 bar abs
0,16 bar abs
Pressure
1,3 bar abs
1,3 bar abs
EDSF5-91
5 bar abs
5 bar abs
and
30 bar abs
30 bar abs
EDSF5-97
100 bar abs
100 bar abs
Level and
-40 to 85°C
60 mbar
According PN/lbs
EDSF7-68
remote seal(s)
see note*
320 mbar
of remote seal
EDSF6-05
1300
mbar
and
5000
mbar
EDSF6-06
30000
mbar
100
bar
200
bar
500
bar
*
Refer to "technical data sheets" about details of process temperature limits of the transmitters.
)RUVSHFL¿FWUDQVPLWWHUVZLWKVWDWLFSUHVVXUH!EDUDVN*HRUJLQ
Protect the transmitter with a security device when the existing application
conditions require it. The transmitter should be installed remote from the
measuring point in the case that the process temperature is too high.