GE-BIN4 WIRING DIAGRAM & LAYOUT
Section A-6
GE-BIN4
GE-BIN4
ELECTRICIAN’S NOTES
(COMMUNICATION WIRING) SHIELDED LOW CAPACITANCE WIRE,
(Capacitance between conductors @ 1Khz = 24pF/ft), TWISTED PAIR (8
twist/ft), AWG #22, 820ft (250m) MAX LENGTH (Ex.: BELDEN 8761).
HIGH VOLTAGE WIRE INSTALLED ACCORDING TO LOCAL
WIRING CODE.
INSTALL LOW VOLTAGE WIRES (COMMUNICATION OR
COMPUTER LINK) AT LEAST 30cm (12 INCHES) AWAY FROM
HIGH VOLTAGE WIRES (120/230VAC, 24VDC). ALWAYS CROSS
HIGH AND LOW VOLTAGE WIRES AT A 90-DEGREE ANGLE.
1 WIRE ONLY PER GREEN TERMINAL. USE WIRE CONNECTOR IF
YOU WANT TO CONNECT MORE THAN 1 WIRE, NO BIGGER THAN
AWG #12, NO SMALLER THAN AWG #28.
CHECK INSTALLATION GUIDE FOR ALARM WIRING.
USE SHIELD FOR SHIELDING PURPOSE ONLY. CONNECT THE
SHIELD TO THE CONTROL CIRCUIT COMMON END ONLY . NEVER
LEAVE THE SHIELD UNCONNECTED AT BOTH ENDS. NEVER
CONNECT BOTH ENDS OF THE SHIELD TO COMMON .
REFER TO THE FEED BIN SCALE INSTALLATION MANUAL FOR
MORE DETAILS OF THE FEED BIN TRANSMITTER MODULE.
A JUMPER MUST BE PLACED ON POSITION 1-2 (ID=1) AT JP4.
2
3
6
8
4
7
5
1