136
ADV200 • Quick start up guide - Specification and installation
10 - Speci
fi
cation
10.1 Environmental Conditions
Installation location
__________________Pollution degree 2 or lower (free from direct sunligth, vi-
bration, dust, corrosive or inflammable gases, fog, vapour
oil and dripped water, avoid saline environment)
Installation altitude
__________________Max 2000m (6562 feet) above sea level;.
Mechanical conditions for installation
___Vibrational stress: EN 60721-3-3 Class 3M1
Operating temperature
______________-10…+40°C (32°…104°F)
Operating temperature (1)
_____40 ... +50°C with derating, (+104 … +122°F with
derating)
Air humidity (operating)
______________5 % to 85 % and 1 g/m
3
to 25 g/m
3
without moisture
condensation or icing (class 3K3 as per EN50178)
Air pressure (operating) [kPa]
__________86 to 106 (class 3K3 as per EN50178)
(1) In menu 4 - DRIVE CONFIG set the Ambient temperature parameter, PAR 564, to 1 (50°C).
10 % derating of output current.
The drive is suitable for use under the environmental service conditions (climate,
mechanical, pollution, etc.) de
fi
ned as usual service conditions according to
EN61800-2.
10.2 Standards
Climatic conditions
__________________EN 60721-3-3
Electrical safety
____________________EN 50178, EN 61800-5-1, UL508C, UL840 degree of
pollution 2
Vibration
__________________________EN 60068-2-6, test Fc.
EMC compatibility
___________________EN61800-3
Protection degree
___________________IP20,
≥
size 7: IP00
Approvals
_________________________
,
L
L
10.3 Accuracy
10.3.1 Current control
Loop sampling time ___________________125
μ
s
Response time ______________________600 - 1600
μ
s
PWM frequency _____________________2, 4, 6, 8, 10, 12 kHz (size dependent)
10.3.2 Speed control
Loop sampling time ___________________125
μ
s
Response time ______________________5 - 10ms
Speed measurement __________________FP, F mode
Speed regulation accuracy _____________FOC with Speed feedback : 0.01 % rated speed
FOC open loop : ± 30 % rated slip
V/F : ± 60 % rated slip
Attention