ADV200 • Quick start up guide - Specification and installation
133
Index Error message shown
on the display
Sub-code
Description
0027H-39
Incompatible software version.
All the parameters present in the memory of the keypad have been transferred
to the drive. The set of parameters transferred refers to a drive with a different
firmware version; therefore, certain parameters may not be updated.
0028H-40
Incompatible drive size.
All the parameters present in the memory of the keypad (excluding those that
depend on the size of the drive), have been transferred to the drive. The parameters
that depend on size maintain their original value.
0029H-41
Error during saving of parameters on the drive.
All the parameters present in the memory of the keypad have been transferred to
the drive. The transfer of one or more parameters has caused an “out of range”
error, or one or more parameters does not exist. At the end of transfer, one or more
parameters may not have been updated.
002AH-42
PLC application release and version not compatible.
All parameters in the keypad memory have been transferred to the drive.
The transferred set of parameters relates to a drive with a PLC application in which
the version and release of the application are different. As a result some of the PLC
application parameters may not be updated.
002BH-43
PLC application not compatible.
All the parameters in the keypad memory except those relating to the PLC applcia-
tion have been transferred to the drive.
The transferred set of parameters relates to a drive with a different PLC application.
As a result none of the PLC application parameters are updated.
Solution:
Recover a set of parameters from a compatible drive (model and size)
10
Options config error
Condition:
may occur at drive start-up, during recognition of the optional cards installed
0001H-1
Non-permissible optional card in slot 1
0002H-2
Non-permissible optional card in slot 2
0004H-4
Non-permissible optional card in slot 3
0010H-16
Conflict slot 1 with slot 2
0020H-32
Conflict slot 1 with slot 3
0040H-64
Conflict slot 2 with slot 3
Solution:
Remove the optional cards from the incorrect slots and insert them in the correct slots
11
Load def plc
Condition:
may occur during loading of the parameter database saved in the Flash of the Mdplc
application
Normally appears at initial power-on after downloading a new application.
If this message is displayed when the drive is already operating, this means that a problem has
occurred in the parameter database saved in Flash.
If this message appears the drive restores the default database, i.e. the one that was downloaded.
0001H-1
The database saved is not valid
Solution:
Set the parameters to the value required and perform
Save parameter
12
Plc cfg error
Condition:
may occur during loading of the Mdplc application
The Mdplc application present on the drive is not run.
0004H-4
The application downloaded has a different Crc on DataBlock and Function table
0065H-101
The application downloaded has an invalid identifier (Info)
0066H-102
The application downloaded has an incorrect task number (Info)
0067H-103
The application downloaded has an incorrect software configuration
0068H-104
The application downloaded has a different Crc on DataBlock and Function table
0069H-105
A Trap error or System error has occurred.
The drive automatically performs a Power-up operation.
The application is not run.
See in Alarm List for further information regarding the error occurred
006AH-106
The application downloaded has an incorrect identifier (Task)