42
Aries Installation and Commissioning manual
16
EXAMPLE VALUES FOR HEAT PUMP SETTINGS FOR
DIFFERENT HEATING NETWORKS
Heating circuit set points
Row number
Control row
Factory
setting
Floor heating
Radiator
heating
Air heating
LP1
LP2
710 1010
Comfort operation set point
20
712 1012
Diminished set point
15
720 1020
Heating curve gradient
0.5
(0.3–0.5)
0.8
(0.5–1.0)
0.8
(0.5–1.0)
740 1040
Supply water min. set point
15
18
15
15
741 1041
Supply water max. set point
45
45
(35–45)
55
(45–60)
55
(45–60)
730 1030
Summer/winter
heating
threshold
16